| Plan Review Notes For Permit 14120142 |
| Permit Number |
14120142 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-04 10:38:51 | 12/4/2014 | | | PROJECT: ARCHITECTURAL TESTING | | | PERMIT#: 14100979 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) CLARIFICATION REQUIRED. THE NOTES AND PANEL SCHEDULE | | | ON SHEET E1 ARER CONFLICTING. THE NOTES CALL FOR AN | | | EXISTING BREAKER TO FEED A NEW SUB-PANEL BUT ALL | | | PANELS, AND FEEDERS ARE INDICATED AS EXISTING. THE ONLY | | | NEW WORK APEARS TO BE THE NEW RECEPTACLES FOR THE | | | PROPSED TEST WALL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|