| 2015-06-19 17:04:18 | BUILDING PLAN REVIEW |
| | PERMIT: 14120130 |
| | ADD: 1901 S. DIXIE HWY. |
| | CONT: SISCACONSTRUCTION |
| | TEL: (561)686-5545 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: FRI. JUNE 19/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET INDICATES UNDER THE CODE ANALYSIS: |
| | 1A-B) COMPLIED. . |
| | |
| | 1C) PROVISO: THE PLANS INDICATE A PROPOSED UNDERGROUND |
| | FIRE LINE TAP.2010 FBC-B 903.1.2 GROUP A2 WHEN THE FIRE |
| | AREA HAS AN OCCUPANT LOAD OF 100 OR MORE FIRE |
| | SPRINKLERS ARE REQUIED. 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA FOR BUILDINGS. 107.3.5.1 COMMERCIAL BUILDINGS |
| | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC |
| | FIRE SPRINKLERS |
| | |
| | 2) SITE PLAN AP 1.0: |
| | |
| | 2A) 3RD REQUEST. ALL 3 VERSIONS OF THIS PLAN SHOWS A |
| | NEW FRONT ENTRY, WITH DOORS THAT SWING OUT OVER THE |
| | PROPERTY LINE. THE CURRENT SET OF DOORS ARE IN SWING |
| | DOORS. 2010 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND |
| | BELOW 8 FEET IN HEIGHT. DOORS AND WINDOWS SHALL NOT |
| | OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 2B) THE CITY HAS AN ISSUE WITH SUBMITTED |
| | DISPROPORTIONATE COST BREAK DOWN FOR THIS PROJECT. THE |
| | PERMIT APPLICATION VALUE IS INDICATED AS $336,000.00 |
| | DOLLARS BUTTHE TOTAL DISPROPORTIONATE COST TOTALS |
| | $304,175.00 DOLLARS. THE MEP SUBCONTRACTORS, FIRE |
| | SPRINKLER AND OTHER MISC. PERMITS CAN'T ADD UP TO |
| | $31,825 DOLLARS. PLEASE HAVE THE CONTRACTOR PROVIDE A |
| | TRUE COST BREAK DOWN OF THE TOTAL JOB COST AND THE COST |
| | ASSOCIATED WITH THE ACCESSIBLE ELEMENTS THAT MAY MEET |
| | DISPROPORTIONATE COST. |
| | 2010 FL. ACCESSIBILTY CODE SEE SECTION 202.4.1 AND |
| | 202.4.1 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR |
| | DESIGNER OF RECORD ON THEIR LETTER HEAD PROVIDE A COST |
| | BREAKDOWN WHERE $67,200.00 DOLLORS WILL BE SPENT IN |
| | ACCESSIBLE UPGRADES. PLEASE NOT THE ORDER IN WHICH THE |
| | FUNDS ARE TO BE SPENT. FL ACC. CODE 202.4.2. (I) AN |
| | ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM |
| | FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV) |
| | ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING |
| | FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | 2C) COMPLIED |
| | |
| | 3) COMPLIED. |
| | |
| | 4) THE OPTION OF DEFERRRED SUBMITTALS IS UP TO THE |
| | CONTRACTOR AND OR THE DESIGNERS, NOT MY REQUEST. IF |
| | EITHER THE CONTRACTOR AND OR DESIGNER WOULD PREFER TO |
| | TAKE ADVANTAGE OF THE DEFERRED SUBMITTALS PLEASE |
| | INDICATE YOU WOULD LIKE TO DO SO AND THE PRODUCT |
| | APPROVALS WILL BE DEFERRED UNTIL AFTER PERMIT ISSUANCE. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS |
| | SYSTEMS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) PROVISO: SUBMIT BEFORE 1ST INSPECTION FOR FOOTINGS. |
| | SHEET S4.0 ALSO HAS STATEMENTS FOR SOILS REPORTS FOR |
| | ALL OF THE NEW FOUNDATIONS FOR THE MEZZANINE LEVEL. THE |
| | ASSUMED SAFE BEARING VALUE OF THE SOILS IS 2500 PSF. |
| | NOTE 3 READS: SOILS SUPPORTING ALL FOOTING MUST BE |
| | INSPECTED AND APPROVED BY A REGISETERD SOILS ENGINEER |
| | BEFORE COMMENCING WORK. APPROVED IN WRITING MUST |
| | INDICATE THE SOIL IS ADEQUATE TO SAFETLY SUSTAIN |
| | SPECIFIED SOIL BEARING PRESSURE. 2010 FBC-B 1803.2 |
| | INVESTIGATIONS REQUIRED. |
| | |
| | 8-10) COMPLIED. |
| | |
| | 12) COMPLIED. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |