| 2015-06-10 09:24:05 | 1) SHT. P1.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE |
| | CUBIC FOOTAGE OF 94,880 FOR THE RESTAURANT. IT IS |
| | UNCLEAR TO ME HOW YOU ARRIVED AT YOUR COMBUSTION AIR |
| | CALCULATIONS. IN ACCORDANCE WITH THE STANDARD METHOD IN |
| | THE 2010 FGC SEC.304.5.1, 50 CU. FT. OF COMBUSTION AIR |
| | IS REQUIRED FOR EACH 1,000 BTU OF THE APPLIANCE RATING. |
| | TAKING THE TOTAL BTU LOAD THAT I HAVE CALCULATED AS THE |
| | BASIS FOR THE REQUIRED COMBUSTION AIR (1,559,000 |
| | DIVIDED BY 1000 = (1,559 ) X (50 CU. FT. ) = 77,950 CU. |
| | FT. OF COMBUSTION AIR REQUIRED. THE CUBIC FOOTAGE OF |
| | THE RESTAURANT ON P1.2 IS SHOWN AS 94,880 AND ALSO AS |
| | 81,900 BEING DIVIDED BY 50 CU.FT.AND ARRIVING AT AN |
| | ALLOWABLE BTU LOAD OF 1,897,000 BTU'S. PLEASE ENLIGHTEN |
| | ME AS I HAVE ABSOLUTELY NO IDEA AS TO HOW THESE REULTS |
| | WERE ATTAINED FOR THE REQUIREMENTS FOR THE COMBUSTION |
| | AIR. THERE IS NO REVISED DRAWING P1.2 THAT WAS |
| | SUBMITTED AS STATED IN YOUR RESPONSE OF 4/20/15. THERE |
| | IS VERSION 2 WHICH IS WHAT MY REVIEW COMMENTS ARE BASED |
| | UPON. CLARIFY. |
| | 2) THE BTU LOAD OF THE APPLIANCES LISTED ON SHT. P1.2 |
| | AND SHT. P0.3 DO NOT CORRELATE NOR DO THE TOTAL BTU'S.I |
| | HAVE ADDED THE BTU'S ON SHT. P1.2 AND IT TOTALS |
| | 1,559,000, NOT 1,649,000 AS SHOWN. CLARIFY. |
| | 3) SHT. P0.3 SHOWS THE BTU LOAD FOR RANGE #2 AS 70,000 |
| | AND SHT. P1.2 HAS THE BTU LOAD AS 140,000. CLARIFY. |
| | 4) SHT. P0.3 - TOTAL GAS CONSUMPTION TABLE SHOWS ONE |
| | (1) RANGE #1 LISTED AND SHT. P1.2 SHOWS TWO (2) RANGE |
| | #1 UNITS LISTED FOR A TOTAL OF 490,000 BTU'S. CLARIFY. |
| | 5) SHT. P0.3 - RANGE #3 IS SHOWN ON THE GAS RISER AND |
| | ON THE GAS CONSUMPTION LIST BUT NOT ON SHT.P1.2. |
| | CLARIFY. |
| | |
| | NOTE: A COMPREHENSIVE GAS REVIEW CANNOT BE DONE UNTIL |
| | ALL THE CORRECT BTU LOADS AND COMBUSTION AIR |
| | CALCULATIONS ARE SUBMITTED.I SUGGEST CONTACTING ME TO |
| | SET UP A MEETING TO REVIEW AND DISCUSS THESE COMMENTS. |
| | |