| 2014-12-22 05:18:26 | 1) SHT.A4.0 - DETAIL #1 - STAFF R.R.- THE HEIGHT OF THE |
| | GRAB BAR ABOVE THE FINISH FLOOR SHALL BE MEASURED TO |
| | THE TOP OF THE GRIPPING SURFACE, NOT TO THE CENTERLINE |
| | OF THE BAR AS SHOWN.2010 FL. ACCESS. CODE SEC.609.4. |
| | 2) LIFE SAFETY PLAN - INDICATE THE PREVIOUS OCCUPANCY |
| | ON THE PLAN. WPB AMEND. TO 2010 FBC SEC.107.2.1.. SEE |
| | THE BUILDING PLAN REVIEW COMMENT. |
| | 3) A SERVICE SINK IS REQUIRED PER TABLE 403.1. |
| | 4) SUBMIT MANUFACTURER SPECIFICATION SHEETS AND |
| | INSTALLATION MANUAL FOR THE TANKLESS WATER HEATERS. THE |
| | TANKLESS WATER HEATERS SHALL BE LISTED AND LABELED PER |
| | THE 2010 FL. GAS CODE SEC. 301.3. |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL |
| | THE GAS APPLIANCES/EQUIPMENT. ALL EQUIPMENT SHALL BE |
| | LISTED AND LABELED PER SEC. 301.3 OF THE 2010 FGC. |
| | 6) SHT. P0.2 - THE SANITARY RISER DOES NOT COMPLY WITH |
| | SEC.909 OF THE FL. PLUMBING CODE FOR THE NUMBER AND |
| | TYPE OF FIXTURES PERMITTED ON A WET VENT. |
| | 7) SHT.P1.1A - A FLOOR DRAIN IS SHOWN IN THE WARE |
| | WASHING AREA (#113) BUT IS NOT SHOWN ON THE GREASY |
| | WASTE RISER ON P0.2.CLARIFY. |
| | 8) SHT.P1.1A - SHOW THE INDIRECT WASTE FROM FIXTURE #7 |
| | TO THE FLOOR DRAIN ON RISER P0.2. |
| | 9) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | TANKLESS WATER HEATERS & ALL THE GAS APPLIANCES ON THE |
| | FIRST FLOOR. 201 FL. GAS CODE SEC.304. |
| | 10) SUBMIT VENTING DETAILS FOR THE TANKLESS WATER |
| | HEATERS. 201 FGC SEC.503.THE PLUMBING PLANS REFER TO |
| | THE MECHANICAL SHEETS FOR DETAILS BUT THERE IS JUST A |
| | PLAN VIEW WITH NO DETAILS. |
| | 11) SUBMIT MANUF. SPECS FOR THE VENTLESS GAS |
| | REGULATORS. WPB AMEND. TO 2010 FBC SEC.107.2.1, FGC |
| | SEC.410.0. |
| | 12) SHOW THE INCREMENTAL BTU/CFH LOAD ON THE GAS PIPING |
| | SYSTEMFROM THE ENTRANCE METER TO THE FURTHEST OUTLET. |
| | 13) WHERE IS PAGE 2 OF 2 FOR THE GREASE INTERCEPTOR |
| | DETAILS.? |
| | 14) THE GREASE TRAPS APPEAR TO BE LOCATED ON LOT 6. IS |
| | THIS PROPERTY OWNED BY THE RESTAURANT? |
| | 15) PROVIDE A LEGEND FOR THE HOT, COLD, HOT WATER |
| | RETURN AND THE TEMPERED WATER. THE RISER SHOWS THE |
| | INDIVIDUAL WATER IDENTIFIED WITH DOTS AND DASHES.WPB |
| | AMEND. TO 2010 FBC SEC.107.2.1 |
| | 16) PROVIDE INFORMATION/DETAILS FOR THE REGULATOR VENT |
| | FOR THE TANKLESS WATER HEATERS. WPB AMEND. TO 2010 FBC |
| | SEC.107.2.1.COMPLY W/ 2010 FGC SEC.410.3.1. |
| | 17) TOILET ROOMS SHALL NOT OPEN DIRECTLY INTO A ROOM |
| | USED FOR THE PREPARATION OF FOOD FOR SERVICE TO THE |
| | PUBLIC. 2010 FL. BLDG. CODE. SEC.1210.5. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |