| 2014-12-23 11:49:22 | 1901 SOUTH DIXIE HIGHWAY |
| | CHANGE OF OCCUPANCY FROM MERCANTILE TO ASSEMBLY |
| | PERMIT #14120130 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING, "FIRE |
| | PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING |
| | (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE |
| | FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY." |
| | |
| | GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE |
| | BUILDING ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL |
| | BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES |
| | IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | CIVIL SITE: NO PARKING SIGNS WILL BE NEEDED ON KANUGA |
| | DRIVE TO PROVIDE FIRE DEPARTMENT ACCESS TO PROPOSED |
| | FIRE DEPARTMENT CONNECTION, BACKFLOW PREVENTER AND |
| | EXISTING FIRE HYDRANT. BACKFLOW PREVENTER WILL NEED TO |
| | BE PROTECTED FROM VEHICULAR TRAFFIC. |
| | |
| | SHEET LS: SECONDARY EXIT (KANUGA DRIVE) DOOR SWINGS |
| | INTO THE PUBLIC RIGHT OF WAY. |
| | |
| | SHEET A1.0: MAIN ENTRY DOOR EQUIPPED WITH THUMB TURN |
| | LOCK. FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| | THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER |
| | LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| | RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| | PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| | AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| | READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| | UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| | SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE |
| | EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH |
| | AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK |
| | IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | SHEET A1.2: AREA AT BOTTOM OF STAIR INDICATED AS |
| | RECEIVING AREA. WHAT SAFE GUARDS WILL BE IN PLACE TO |
| | ENSURE THE EXIT STAIR (SINGLE MEANS OF EGRESS) IS NEVER |
| | BLOCKED OR OBSTRUCTED? |
| | |
| | SHEET A2.0: THE CEILING AND STRUCTURE HEIGHTS CANNOT BE |
| | DETERMINED FOR THE UPPER LEVEL. HEAD CLEARANCES OF |
| | 7'-6" SHALL BE PROVIDED AND INDICATED ON THE PLANS. |
| | |
| | SHEET A2.0: PROVIDE A STORAGE LAYOUT. IN GENERAL, |
| | INDICATE THE COMMODITIES TO BE STORED, THE QUANTITY TO |
| | BE STORED, AND THE HEIGHT OF STORAGE, ETC. |
| | |
| | SHEET P2.1: EQUIPMENT SCHEDULE INDICATES A CHARCOAL |
| | GRILL (ITEM #74). SOLID FUEL AND FIRE PROTECTION |
| | INFORMATION AND DETAILS NEEDED FOR APPROVAL. |
| | |
| | FIRE PROTECTION: FOR ISSUANCE OF A GENERAL BUILDING |
| | PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING |
| | CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION |
| | DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE |
| | AUTOMATIC FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE |
| | CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |