| Plan Review Notes For Permit 14120130 |
| Permit Number |
14120130 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-27 12:53:44 | 14120130 | | | 1901 S DIXIE HWY | | | INTERIOR IMPROVEMENT | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENT. | | | | | | VERIFY THIS BUILDING WILL HAVE ONLY ONE POINT OF | | | ELECTRICAL SERVICE. INDICATE | | | THE INTENDED USE FOR THE ELECTRICAL PANELS SHOW ON THE | | | WEST EXTERIOR ELEVATION OF SHEET A3. NEC 230.2 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | | SYSTEMS, SECURITY, SITE LIGHTING AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | | | | | | | |
|