| 2014-12-28 12:48:53 | 1ST REVIEW: FBC 2010 |
| | |
| | THE OVERALL SCOPE OF WORK AND WHAT IS PROPOSED AS NEW |
| | IS UNCLEAR. ACCORDINGLY THE VALUATION IS NOT PRESUMED |
| | TO BE ACCURATE. PROVIDE A SCOPE OF WORK AND A COST |
| | BREAKDOW IF THAT MAY BE HELPFUL. ADDITIONALLY, IT IS |
| | UNCLEAR WHO THE MECHANICAL DESIGNER OF RECORD IS AND IF |
| | THE DUCT SYSTEM, HAND DRAWN, ON SHEET A-1 IS NEW OR |
| | EXISTING. IS THE ROOF COVERING TO BE REPLACED? IS THERE |
| | AN ADDITION PROPOSED? PLAN INDICATES 1,152 SF RECORSD |
| | SHOW EXISTING TOTAL UNDER AIR IS 720 SF. PLEASE PROVIDE |
| | A SITE PLAN OR SURVEY. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN |
| | |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. (MECHANICAL PLAN) |
| | |
| | FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE |
| | SETBACKS AND BUILDING SEPARATION. |
| | |
| | ADDITIONALLY, IT SEEMS YOU ARE REPLACING SOME WINDOWS. |
| | THE PRODUCT APPROVAL SUBMITTED HAS AN "OREIAL " & AN |
| | "EQUAL SPLIT" OPTION, WHICH IS PROPOSED. NO PRODUCT WAS |
| | SUBMITTED FOR THE MULLIONS. ADDITIONALLY, |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING,(IF APPLIABLE) & WINDOW |
| | MULLION. |
| | |
| | THE ENERGY SUBMITTAL WILL BE EVALUATED UPON |
| | RESUBMITTAL. |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |
| | |