| 2015-12-30 15:10:07 | BUILDING PLAN REVIEW |
| | PERMIT: 14120093 |
| | ADD: 809 6TH ST. |
| | CONT: MIJO CONSTRUCTION |
| | TEL: (561)246-0411 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: WED. DEC. 30/2015 |
| | ACTION: DENIED |
| | |
| | 1) COVER SHEET: |
| | 1A-D) COMPLIED. |
| | |
| | 1E) 3RD REQUEST. PLEASE REVIEW 2010 FBC-B 903.2.8 AN |
| | AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH |
| | 903.3 SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A |
| | GROUP R FIRE AREA. |
| | SEE 2010 FBC-B 903.3.1.2 NFPA 13 R SPRINKLER SYSTEMS. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.1 MINIMUM |
| | PLAN REVIEW CRITERIA COMMERCIAL BUILDING. |
| | .5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS |
| | |
| | 2) COMPLIED. |
| | |
| | 3) 3RD REQUEST. SHEETS A1 & A2 FAIL TO IDENTIFY 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.8 MINIMUM |
| | PLAN REVIEW CRITERIA COMMERCIAL BUILDING. |
| | .8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | WIND REQUIREMENTS PROVIDE THE WIND DESIGN CRITERIA, |
| | BUILDING ENVELOPE/ PRODUCT APPROVALS |
| | |
| | STRUCTURAL CALCULATIONS (IF REQUIRED) 2010 EXT. BLDG. |
| | CODE LEVEL III 807.4. 1 THRU 3. LIVE LOADS FBC-B TABLE |
| | 1607.1. |
| | FLOOR SYSTEMS PROVIDE FLOOR LOADING |
| | STAIR SYSTEMS |
| | HANDRAILS |
| | |
| | 4) COMPLIED. |
| | 5) 3RD REQUEST. SHEETS A1 & A2 FAIL TO IDENTIFY 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.11. |
| | INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) SEE |
| | 2010 FBC-B TABLE 803.9. |
| | |
| | |
| | 6) FL. ENERGY CODE: |
| | 6A) COMPLIED. |
| | |
| | 6B)(1) SHEET D-1 THE 1ST FLOOR IS MISSING FLOOR |
| | INSULATION UNDER THE FIRST FLOOR. 2010 FBC-ENERGY CODE |
| | 402.4.1, 402.2.6 . |
| | |
| | 6B)(2) A) 3RD REQUEST. FBC-B 2010 1207.3 |
| | STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | |
| | B)3RD REQUEST. FBC-B 2010 1207.2 1207.2 AIR-BORNE |
| | SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | C) 3RD REQUEST. FLAME SPREAD- FBC-B 2010 603.1.2 |
| | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | TYPE III-TYPE V CONSTRUCTION: |
| | 719.2 CONCEALED INSTALLATION. |
| | INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| | BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| | |
| | |
| | |
| | 6)(3) COMPLIED. |
| | |
| | 6C) 3RD REQUEST. SHEET D-1 COMMON WALL DETAIL INDICATES |
| | CODE COMPLIANCE FOR FL ENERGY CODE 402.2.12.2, PLEASE |
| | PROVIDE COMPLIANCE WITH 2010 FBC-B 1207.2 AIR-BORNE |
| | SOUND. WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE. |
| | |
| | 6D) 3RD REQUEST. SHEET D-1 TENANT WALL/ FLOOR DETAIL |
| | INDICATES THE USE OF 3 INCH ATTEN. BATT R-30 BATT |
| | INSULATION, PLEASE PROVIDE COMPLIANCE WITH FBC-B 1207.3 |
| | STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 6E-F) COMPLIED. |
| | |
| | 7-12) COMPLIED. |
| | |
| | 13) SHEET D1 PLEASE PROVIDE CODE COMPLIANCE FOR THE 2ND |
| | FLOOR TENANTS HOW THE SPACE ABOVE THE CEILING& TENANT |
| | WALL SEPARATION WILL BE MADE CODE COMPLIANT WITH FBC-B |
| | 709.4 OR EXCEPTIONS. |
| | |
| | 14)COMPLIED. ROOF: FIBERGLASS SHINGLES. |
| | |
| | 15) DEFERRED SUBMITTAL: PLEASE PROVIDE THE PRODUCT |
| | APPROVAL ON ICYNENE, WITHIN THE ICC REPORT CIRCLE WHICH |
| | SUB-SYSTEM YOU INTEND ON USING IN ACCORDANCE WITH THE |
| | MANUFACTURER?S INSTRUCTIONS. PLEASE ALSO SEE 2010 FBC-B |
| | 2603.4.1.6 IGNITION BARRIER REQUIREMENT, DIFFERENT FROM |
| | THE THERMAL BARRIER REQUIREMENTS. |
| | |
| | 16) 3RD REQUEST. SHEET D-1 INTERIOR FINISHES, WITH THE |
| | DESIGNER NOT LISTING THE OCCUPANCY TYPE R-1 OR R-2 THE |
| | COMPLIANCE WITH TABLE 803.9 IS A UNKNOWN, ALSO IF FIRE |
| | SPRINKLERED OR NOT. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.11. |
| | INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) SEE |
| | 2010 FBC-B TABLE 803.9. |
| | |
| | 17) 3RD REQUEST. 2010 EXISTING BUILDING CODE, LEVEL III |
| | ALTERATION PLEASE REVIEW 804.1 AUTOMATIC SPRINKLER |
| | SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED |
| | IN ALL WORK AREAS IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. THE FIRE SPRINKLER PLANS NEED |
| | TO BE SUBMITTED PROVIDE THE HYDRAULIC CALCS FOR THE |
| | FIRE SPRINKLERS AND A SCHEMATIC LAYOUT. THE FIRE |
| | SPRINKLER SHOP DRAWINGS WILL BE SUBMITTED UNDER |
| | SEPARATE PERMIT. |
| | |
| | 2010 FBC-B [F] 903.2.8 GROUP R. AN AUTOMATIC SPRINKLER |
| | SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL |
| | BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R |
| | FIRE AREA. |
| | |
| | 2010 FBC-B F] 903.3 INSTALLATION REQUIREMENTS. |
| | AUTOMATIC SPRINKLER SYSTEMS SHALL BE DESIGNED AND |
| | INSTALLED IN ACCORDANCE WITH SECTIONS 903.3.1 THROUGH |
| | 903.3.6. |
| | |
| | 18) COMPLIED. SHEET A3 PRESSURES FOR WINDOWS AND DOORS. |
| | |
| | 19) COMPLIED. EGRESS WINDOWS. |
| | |
| | 20-22) DEFERRED SUBMITTALS. 107.3.4.2 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS/ MULLIONS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | |
| | 21)COMPLIED. ROOFING EXISTING NOT REPLACING |
| | |
| | 22) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |