| Plan Review Notes For Permit 14120093 |
| Permit Number |
14120093 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-26 11:02:08 | 2ND REVIEW: FBC 2010 MECHANICAL | | | | | | 1) SHEET M-1: THE RETURN AIR GRILLS IN EACH OF THE NEW | | | AHU CLOSET DOORS 1ST AND 2ND FLOOR ARE UNDERSIZED PER | | | SECTION 601.4 (EXCEPTION 2) FBC-10 MECHANICAL. A | | | MINIMUM 24 X 24" FOR THE 3-TON SYSTEM, AND MINIMUM 20 X | | | 20" GRILLS ARE REQUIRED FOR THE 2-TON SYSTEMS: PLEASE | | | CORRECT. | | | 2) M-1: THE 2ND FLOOR UNITS ARE MISLABELED UNITS #3 & | | | #4: REFERENCE THE ARCHITECTURAL AND LIFE SAFETY PLAN | | | SHEETS. | | | 3) M-1: THE FLOOR PLAN LAYOUTS AND ROOM IDENTIFICATIONS | | | SHOWN ON THE 2ND FLOOR MECHANICAL PLAN DO NOT MATCH THE | | | ARCHITECTURAL AND LIFE SAFETY PLAN LAYOUTS: PLEASE | | | REVISE. | | | 4) M-1: SHOW THE DRYER IN THE 2ND FLOOR NORTH UNIT (SEE | | | ARCH. SHEET 2) AND PROVIDE EXHAUST VENTILATION DETAILS | | | INCLUDING THE TYPE AND SIZE OF DUCT, DUCT RUN, AND | | | TERMINATION LOCATION. CLARIFY IF LAUNDRY WILL BE | | | INSTALLED IN THE OTHER TWO UNITS AND PROVIDE DRYER | | | EXHAUST DETAILS (IF APPLICABLE). | | | 5) PLEASE NOTE: ADDITIONAL COMMENTS MAY FOLLWO PENDING | | | RE-SUBMITTAL OF CORRECTED PLANS. |
|