| 2015-08-25 19:54:10 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. THOUGH YOUR PANEL SCHEDULES REFLECTS A WATER HEATER | | | IN THE DIRECTORIES AND LOAD CALCS IT IS NOT REFLECTED | | | ON THE FLOOR PLANS OF EITHER UNIT. | | | 2. ALL CEILING LUMINARY OUTLETS SHALL BE LISTED TO | | | SUPPORT 50 LBS. | | | 3. INDICATE THE APPLICABLE SCALE FOR THE DRAWINGS TO BE | | | ABLE TO CONFIRM PROPER OUTLET PLACEMENT. | | | 4. UNIT 2 STAIRWAY IS MISSING THE DUAL CONTROL REQUIRED | | | BY NEC 210.70 FOR THE LIGHTING | | | 5. VERIFY THE LOAD CALCS AS SUBMITTED. | | | 6. EACH A/C CONDENSING UNIT REQUIRES ITS OWN SERVICE | | | GFI RECEPTACLE SERVED FROM ITS RESPECTIVE PANEL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|