| 2014-12-06 06:13:09 | 1) THE SANITARY RISER SHOWS A LAVATORY IN THE BATHROOM | | | BY BEDROOM # 3 IN UNIT # 2 AND ALSO IN UNIT #4 BUT | | | THERE IS NO LAVATORY SHOWN ON THE FLOOR PLAN. CLARIFY. | | | 2) TABLE 403.1 OF THE 2010 FL. PLUMBING CODE REQUIRES 1 | | | AUTOMATIC CLOTHES WASHER CONNECTION PER 20 DWELLING | | | UNITS. SHOW THE LOCATION OF THIS CONNECTION ON THE | | | FLOOR PLAN | | | 3) THE LAYOUT OF THE FIXTURES ON THE RISER DIAGRAM DO | | | NOT CORRELATE WITH THE FLOOR PLAN. WPB AMEND. TO 2010 | | | FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|