| 2014-12-08 10:15:46 | BUILDING PLAN REVIEW |
| | PERMIT: 14120093 |
| | ADD: 809 6TH ST. |
| | CONT: MIJO CONSTRUCTION |
| | TEL: (561)246-0411 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. DEC. 08/2014 |
| | ACTION: DENIED |
| | |
| | 1) COVER SHEET: |
| | 1A) THE DESIGNER OF RECORD FAILS TO IDENTIFY WHICH |
| | CODES THESE PLANS WERE DESIGNED UNDER(DESIGN CRITERIA) |
| | AND TO WHAT LEVEL THIS BUILDING IS BEING ALTERED? OR A |
| | CHANGE OF OCCUPANCY? 2010 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 107. 3.5.1.1 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL |
| | BUILDING. |
| | |
| | 1B) THE COVERSHEET ALSO FAILS TO IDENTIFY (DESIGN |
| | CRITERIA) THE OCCUPANCY TYPE AND IF TRANSIENT OR |
| | NON-TRANSIENT. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107. |
| | 3.5.1.2 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL |
| | BUILDING. 2010 FBC-B 310.1. |
| | |
| | 1C) THE COVERSHEET ALSO FAILS TO IDENTIFY (DESIGN |
| | CRITERIA) THE MINIMUM BUILDING TYPE THIS STRUCTURE CAN |
| | BE DESIGNED TO? 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107. |
| | 3.5.1.3 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL |
| | BUILDING MINIMUM CONSTRUCTION TYPE. |
| | |
| | 1D) THE COVERSHEET ALSO FAILS TO IDENTIFY (DESIGN |
| | CRITERIA) 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107. |
| | 3.5.1.4 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL |
| | BUILDING. |
| | .4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| | RESISTANCE |
| | |
| | 1E) THE COVERSHEET ALSO FAILS TO IDENTIFY (DESIGN |
| | CRITERIA) IF THIS OCCUPANCY IS FIRE SPRINKLERED OR NOT? |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.1 MINIMUM |
| | PLAN REVIEW CRITERIA COMMERCIAL BUILDING. |
| | .5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | EARLY WARNING SMOKE EVACUATION SYSTEMS |
| | SCHEMATIC FIRE SPRINKLERS |
| | STANDPIPES |
| | PRE-ENGINEERED SYSTEMS |
| | RISER DIAGRAM |
| | |
| | 2) SHEETS A1 & A2 FAILS TO IDENTIFY (DESIGN CRITERIA) |
| | EGRESS COMPONENTS, 2010 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 107. 3.5.1.7 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL |
| | BUILDING. |
| | . 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE |
| | IN A LIFE SAFETY PLAN: |
| | OCCUPANCY LOAD |
| | GROSS |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | SPECIFIC OCCUPANCY REQUIREMENTS |
| | CONSTRUCTION REQUIREMENTS |
| | |
| | 3) SHEETS A1 & A2 FAIL TO IDENTIFY 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 107. 3.5.1.8 MINIMUM PLAN REVIEW |
| | CRITERIA COMMERCIAL BUILDING. |
| | .8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | WIND REQUIREMENTS |
| | BUILDING ENVELOPE |
| | STRUCTURAL CALCULATIONS (IF REQUIRED) 2010 EXT. BLDG |
| | CODE LEVEL III 807.4. 1 THRU 3. |
| | WALL SYSTEMS |
| | FLOOR SYSTEMS |
| | ROOF SYSTEMS |
| | STAIR SYSTEMS & HANDRAILS |
| | |
| | 4) SHEETS A1 & A2 FAIL TO IDENTIFY 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 107. 3.5.1.10 |
| | WHEN THIS STRUCTURE WAS BUILT, IF FAIR HOUSING AND OR |
| | FL. ACCESSIBILITY APPLY AND ALL APPLICABLE CODE |
| | SECTIONS. |
| | |
| | 5) SHEETS A1 & A2 FAIL TO IDENTIFY 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 107. 3.5.1.11 |
| | 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | LIGHT AND VENTILATION |
| | SANITATION |
| | TOTAL SQ. FT. PER SLEEPING ROOM & SQ. FT. PER KITCHEN & |
| | LIVING RM. |
| | |
| | 6) FL. ENERGY CODE: |
| | 6A) THERE ARE 4 DWELLING UNITS IN THIS BUILDING, UNITS |
| | 1-4, ONLY CALCULATIONS FOR UNIT # 2 WERE SUBMITTED. |
| | PLEASE SUBMIT ENERGY CALCULATIONS FOR ALL UNITS. |
| | |
| | 6B)(1) SHEET D-1 THE 2 STORY EXTERIOR WALL DETAIL IS |
| | MISSING THE FLOOR INSULATION UNDER THE FIRST FLOOR. |
| | 2010 FBC-ENERGY CODE 402.4.1 & 402.2.6. |
| | |
| | 6B)(2) THE SHEET A2, A3 OR D1 INDICATE THE USE OF FLOOR |
| | INSULATION UNDER THE FLOOR OF BEDROOM # 2 IN UNIT # 3. |
| | 2010 FBC-ENERGY CODE 402.4.1 & 402.2.6. |
| | |
| | 6)(3) THE ENERGY CALCULATION TAKES THIS STRUCTURE AS A |
| | SLAB ON GRADE, PLEASE CORRECT. 2010 FBC-ENERGY CODE |
| | 402.4.1 & 402.2.6. |
| | |
| | 6C) SHEET D-1 COMMON WALL DETAIL INDICATES CODE |
| | COMPLIANCE FOR FL ENERGY CODE 402.2.12.2, PLEASE |
| | PROVIDE COMPLIANCE WITH 2010 FBC-B 1207.2 AIR-BORNE |
| | SOUND. WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE. |
| | |
| | 6D) SHEET D-1 TENANT WALL/ FLOOR DETAIL INDICATES THE |
| | USE OF 3 INCH ATTEN. BATT R-30 BATT INSULATION, PLEASE |
| | PROVIDE COMPLIANCE WITH FBC-B 1207.3 STRUCTURE-BORNE |
| | SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 6E) THE ENERGY CALCULATIONS INDICATE A SHGC OF 0.5 |
| | PLEASE PROVIDE DOCUMENTATION, FL ENERGY CODE TABLE |
| | 402.1.1 GLAZED FENESTRATION 0.30. |
| | |
| | 6F) NOTE SHEET A2 DOES NOT SHOW ATTIC ACCESS NOR |
| | COMPLIANCE WITH: |
| | 2010 FBC-B 1209.2 ATTIC ACCESS. |
| | 2010 FBC-ENERGY 402.2.3. |
| | |
| | 7) SHEET A1 STAIR TO UNIT # 3 ON THE SECOND FLOOR, IT |
| | APPEARS THIS UNIT IS MISSING A FRONT DOOR TO THE UNIT, |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1. 7. |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:DOORS. |
| | |
| | 8) SHEET A1 STAIR # 3 ONLY SHOWS ONE SIDE OF THE |
| | STAIRWELL WITH A FIRE RATED WALL. FBC-B 1022.1 |
| | |
| | 9) SHEET A1 STAIR # 3 IS MISSING THE CEILING |
| | INFORMATION BELOW THE STAIR AND ENCLOSURES UNDER |
| | STAIRWAYS ARE TO COMPLY WITH FBC-B 1009.6.3. |
| | |
| | 10) SHEET A1 STAIR # 3 ALSO DOES NOT INDICATE FIRE |
| | BLOCKING. |
| | |
| | 11) SHEET SHEET D1 DETAIL FOR THE TENANT SEPARATION |
| | WALL SHOWS THE HORIZONTAL SEPARATION BETWEEN THE 1ST |
| | FLOOR UNITS & 2ND FLOOR UNITS THE EXTERIOR WALL DETAIL |
| | SHOWS A 2 LAYERS OF 5/8 TYPE X ON THE CEILING. WHAT |
| | BOTH DETAILS FAIL TO PROVIDE IS THROUGH THE CAVITIES IN |
| | THE FLOOR TRUSSES HOW THE FIRE PARTITION BETWEEN THE |
| | UPSTAIRS UNITS 3 & 4 OCCURRS IN THE FLOOR TRUSS, TRUSS |
| | SYSTEM. 439.2 SEE SECTION 709.4 CONTINUITY. IF THE |
| | PARTITIONS ARE NOT CONTINUOUS TO THE SHEATHING, DECK OR |
| | SLAB, AND WHERE CONSTRUCTED OF COMBUSTIBLE |
| | CONSTRUCTION, THE SPACE BETWEEN THE CEILING AND THE |
| | SHEATHING, DECK OR SLAB ABOVE SHALL BE FIREBLOCKED OR |
| | DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS 717.2 AND |
| | 717.3 AT THE PARTITION LINE. |
| | |
| | 12A) SHEET D1 UPPER RIGHT CORNER OF PLANS INDICATES A |
| | CMU STEM WALL DETAIL. IF THIS DETAIL IS TO BE USED IN |
| | SHOWING CODE COMPLIANCE FOR 709.4 FIRE PARTIONS EXTEND |
| | FROM THE TOP OF FOUNDATIONS THEN THERE SHOULD BE A |
| | SECTION THROUGH THE 1ST FLOOR SHOWING THE STEMWALL & |
| | FOOTER UNDER THE TENANT SEPARATION WALL. 2010 FBC-B |
| | 709.4. |
| | |
| | 12B) IF THIS WILL REQUIRE A NEW STEM WALL CONSTRUCTION |
| | THEN IN ONE OF THE TENANT SPACES A NEW ACCESS WILL ALSO |
| | BE REQUIRED TO THE SPACE BENEATH THE FLOOR |
| | SYSTEM.1203.3. |
| | |
| | 13) SHEET D1 PLEASE PROVIDE CODE COMPLIANCE FOR THE 2ND |
| | FLOOR TENANTS HOW THE SPACE ABOVE THE CEILING WILL BE |
| | MADE CODE COMPLIANT WITH FBC-B 709.4 OR EXCEPTIONS. |
| | |
| | 14) THE ENERGY CALCULATIONS , SHEETA2 & D1PLANS |
| | INDICATE THE USE OF CONCRETE ROOF TILE. IS THERE |
| | CURRENTLY CONCRETE ROOF TILE ON THE ROOF NOW OR IS |
| | THERE SHINGLES? |
| | IF THERE IS PRESENTLY SHINGLES THE ADDITIONAL LOADING |
| | DUE TO THE ROOF TILE WILL NEED TO BE REVIEWED BY THE |
| | ENGINEER OF RECORD TO DETERMINE IF THE EXISTING ROOF |
| | FRAMING SYSTEM WILL ACCEPT THE NEW LOADS WITH OUT ANY |
| | EXTRA BRACING. 2010 FBC-EXISTING DLDG. CODE 807.4.2 |
| | SUBSTANTIAL STRUCTURAL ALTERATION. |
| | WHERE MORE THAN 30 PERCENT OF THE TOTAL FLOOR AND ROOF |
| | AREAS OF THE BUILDING OR STRUCTURE HAVE BEEN OR ARE |
| | PROPOSED TO BE INVOLVED IN STRUCTURAL ALTERATION WITHIN |
| | A 12-MONTH PERIOD, THE EVALUATION AND ANALYSIS SHALL |
| | DEMONSTRATE THAT THE ALTERED BUILDING OR STRUCTURE |
| | COMPLIES WITH THE FLORIDA BUILDING CODE, BUILDING FOR |
| | WIND LOADING. |
| | |
| | 15) SHEET D1 EXTERIOR WALL DETAIL SHOWS A SOFFIT BUT |
| | DOES NOT INDICATE HOW THE ATTIC VENTILATION WILL BE |
| | COMPLIED WITH, NOTE THERE WILL NOT BE CROSS VENTILATION |
| | BECAUSE OF THE TENANT SEPARATION WALL OR DRAFTSTOPPING, |
| | WHICHEVER THE DESIGNER OF RECORD ELECTS TO USE. SEE |
| | 2010 FBC-B A MINIMUM OF 1 INCH (25 MM) OF AIRSPACE |
| | SHALL BE PROVIDED BETWEEN THE INSULATION AND THE ROOF |
| | SHEATHING. THE NET FREE VENTILATING AREA SHALL NOT BE |
| | LESS THAN 1/300 OF THE AREA OF THE SPACE VENTILATED, |
| | WITH 50 PERCENT OF THE REQUIRED VENTILATING AREA |
| | PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF |
| | THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM) |
| | ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE |
| | REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. |
| | |
| | 16) SHEET D-1 INTERIOR FINISHES, WITH THE DESIGNER NOT |
| | LISTING THE OCCUPANCY TYPE R-1 OR R-2 THE COMPLIANCE |
| | WITH TABLE 803.9 IS A UNKNOWN, ALSO IF FIRE SPRINKLERED |
| | OR NOT. |
| | |
| | 17) 2010 EXISTING BUILDING CODE, LEVEL III ALTERATION |
| | PLEASE REVIEW 804.1 AUTOMATIC SPRINKLER SYSTEMS. |
| | AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED IN ALL |
| | WORK AREAS IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 2010 FBC-B [F] 903.2.8 GROUP R. AN AUTOMATIC SPRINKLER |
| | SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL |
| | BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R |
| | FIRE AREA. |
| | |
| | 2010 FBC-B F] 903.3 INSTALLATION REQUIREMENTS. |
| | AUTOMATIC SPRINKLER SYSTEMS SHALL BE DESIGNED AND |
| | INSTALLED IN ACCORDANCE WITH SECTIONS 903.3.1 THROUGH |
| | 903.3.6. |
| | |
| | 18) SHEET A3 THE COMPONENTS AND CLADDING PRESSURES FOR |
| | THE WINDWOWS AND DOORS DOES NOT PROVIDE FOR WHAT SQ. |
| | FT. AREA THESE PRESSURES ARE RATED, 10 SQ. FT. OR 20 |
| | SQ. FT.? BATHROOM WINDOWS ARE NOT 20 SQ. FT IN AREA, |
| | WHAT THE MEAN ROOF HEIGHT IS AND ADJUSTMENT FACTOR FOR |
| | THIS MEAN ROOF HEIGHT IS. FBC-B 1609.1.1/ TABLE |
| | 1609.7(2). |
| | |
| | 19) SHEET A3, PLEASE PROVIDE THE WINDOW SIZES IN INCHES |
| | NOT 25 SH, PLEASE PROVIDE CODE COMPLIANCE FOR 2010 |
| | FBC-B : |
| | |
| | 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE |
| | OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 |
| | SQUARE FEET (0.53 M2). |
| | EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR EMERGENCY |
| | ESCAPE AND RESCUE GRADE-FLOOR OPENINGS SHALL BE 5 |
| | SQUARE FEET (0.46 M2). |
| | |
| | 1029.2.1 MINIMUM DIMENSIONS. |
| | THE MINIMUM NET CLEAR OPENING HEIGHT DIMENSION SHALL BE |
| | 24 INCHES (610 MM). THE MINIMUM NET CLEAR OPENING WIDTH |
| | DIMENSION SHALL BE 20 INCHES (508 MM). THE NET CLEAR |
| | OPENING DIMENSIONS SHALL BE THE RESULT OF NORMAL |
| | OPERATION OF THE OPENING. |
| | |
| | 20) SHEET A1 LIST THERE ARE PRODUCT APPROVALS SUBMITTED |
| | WITH THESE PLANS. NO PRODUCT APPROVALS WERE SUBMITTED. |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS/ MULLIONS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | |
| | 21) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.2 FOR |
| | ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| | DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| | TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| | OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE |
| | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 22) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |