| Plan Review Notes For Permit 14120085 |
| Permit Number |
14120085 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-01-27 16:23:08 | PROVISO: | | | | | | EVIDENCE OF EXISTING OPENING PROTECTION OR A REVISION | | | OR SEPARATE PERMIT IS REQUIRED PER THE FOLLOWING | | | SECTION TO PROVIDE: | | | FBC - R301.2.1.2 PROTECTION OF OPENINGS. | | | WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS | | | REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM | | | WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR | | | WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE | | | LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12 | | | OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN. | | | GARAGE DOOR GLAZED OPENING PROTECTION FOR WINDBORNE | | | DEBRIS SHALL MEET THE REQUIREMENTS OF AN APPROVED | | | IMPACT RESISTING STANDARD OR ANSI/DASMA 115. | | | | | | ADDITIONALLY, THE APPLICANT WAS UNABLE TO PROVIDE A | | | PLAN OF BETTER QUALITY AND CLARITY. IN THE EVENT THE | | | PLANS ARE INSUFFICIENT FOR THE USE OF THE INSPECTOR, | | | THE INSPACTOR MAY REQUIRE ADDITIONAL REVISIONS. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|