| Date |
Text |
| 2014-12-19 15:54:54 | 1ST REVIEW: FBC 2010 |
| | |
| | THE SUBMITTED PLANS LACK CLARITY AND REQUIRED DETAIL. |
| | |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE |
| | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |
| | FBC 107- PROVIDE WALL SECTIONS DEMONSTRATING PROPOSED |
| | MATERIALS AND DIMENSIONS OF THE PROPOSED NEW WALL |
| | CONFIGURATION. |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE A WINDOW SUBMITTAL FOR THE NEW |
| | WINDOWS. |
| | |
| | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO |
| | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |