| 2014-12-22 13:50:32 | 12/22/2014 |
| | PROJECT: 401 S. DIXIE STE302 |
| | PERMIT#: 14120085 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS.1ST |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 505.2 LIGHTING CONTROLS (MANDATORY). LIGHTING |
| | SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN |
| | SECTIONS 505.2.1, 505.2.2, 505.2.3 AND 505.2.4. |
| | |
| | 2) FLOOR BOX SHALL BE APPROVED FOR INSTALLATION IN A |
| | FIRE RATED FLOORE/CEILING. NEC 110.3(B) |
| | A.) FBC 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR, |
| | FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A |
| | ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS |
| | 713.4.1.1 THROUGH 713.4.1.4. PENETRATIONS IN HORIZONTAL |
| | SMOKE BARRIERS SHALL ALSO COMPLY WITH 713.5. |
| | B.) FBC 713.4.1.1 THROUGH PENETRATIONS. THROUGH |
| | PENETRATIONS OF FIRE-RESISTANCE-RATED HORIZONTAL |
| | ASSEMBLIES SHALL COMPLY WITH SECTION 713.4.1.1.1 OR |
| | 713.4.1.1.2. |
| | C.) FBC 713.4.1.1(3) PENETRATIONS BY LISTED ELECTRICAL |
| | BOXES OF ANY MATERIAL, PROVIDED SUCH BOXES HAVE BEEN |
| | TESTED FOR USE IN FIRE-RESISTANCE-RATED ASSEMBLIES AND |
| | INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS INCLUDED |
| | IN THE LISTING. |
| | |
| | 3) MULTIWIRE CIRCUITS, NOT PERMITTED. INDIVIDUAL |
| | PARTITIONS OR GROUPS OF INTERCONNECTED INDIVIDUAL |
| | PARTITIONS SHALL NOT CONTAIN MULTIWIRE CIRCUITS.NEC |
| | 605.8 (D) |
| | A.) WIRED PARTITIONS THAT ARE FIXED (SECURED TO |
| | BUILDING SURFACES) SHALL BE PERMANENTLY CONNECTED TO |
| | THE BUILDING ELECTRICAL SYSTEM BY ONE OF THE WIRING |
| | METHODS OF CHAPTER 3. MULTIWIRE BRANCH CIRCUITS |
| | SUPPLYING POWER TO THE PARTITION SHALL BE PROVIDED WITH |
| | A MEANS TO |
| | DISCONNECT SIMULTANEOUSLY ALL UNGROUNDED CONDUCTORS AT |
| | THE PANELBOARD WHERE THE BRANCH CIRCUIT ORIGINATES. NEC |
| | 605.6 FIXED-TYPE PARTITIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | SEE LINK: HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS |
| | /SITES/33/2013/09/APPLICATION_RESUBMITTAL_FORM_04132010 |
| | .PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |