| 2014-12-05 11:36:53 | BUILDING PLAN REVIEW |
| | PERMIT: 14120084 |
| | ADD: 401 S. DIXIE HWY. SUITE # 302 |
| | CONT: IBIS BUILDING |
| | TEL: (561)318-8408 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. DEC. 05/2014 |
| | ACTION: DENIED. |
| | |
| | 1) SHEET A-1.0 THE DOOR SCHEDULE LIST THE FRONT ENTRY |
| | DOORS AS TYPE E, A EXISTING DOOR. THE LIFE SAFETY |
| | SHEETS INDICATE THIS TO BE A 1 HOUR FIRE RATED WALL, |
| | 2010 FBC-B TABLE 715.4 OPENING PROTECTIVES A 1 HR. FIRE |
| | RATED CORRIDORR REQUIRES A 20 MIN. OPENING PROTECTIVE. |
| | |
| | 2) SHEET A-1.0 THE FLOOR PLANS IDENTIFIES THE WINDOWS |
| | WITH A IDENTIFICATION TAG # 1. THE DOOR AND WINDOW |
| | SCHEDULE UNDER THE HEADING # 1 IDENTIFIES WINDOW & DOOR |
| | SCHEDULE IDENTIFIES THE WINDOWS TYPE AS A B3. SHEET |
| | A-2.0 IDENTIFIES THE WINDOW TYPE B3 AS A WOOD FRAMED |
| | DOOR WITH TEMPERED GLASS. |
| | THE WINDOW TYPE 1 IS NOT IDENTIFIED NOR DOES THE ISSUE |
| | OF THE GLAZING BEING A HAZARDOUS LOCATION. SEE 2010 |
| | FBC-B 2406.4; |
| | |
| | 6. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL |
| | ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF |
| | THE GLAZING IS WITHIN A 24-INCH (610 MM) |
| | ARC OF EITHER VERTICAL EDGE OF THE DOOR IN A CLOSED |
| | POSITION AND WHERE THE BOTTOM EXPOSED EDGE OF THE |
| | GLAZING IS LESS THAN 60 INCHES (1524 MM) |
| | ABOVE THE WALKING SURFACE. |
| | |
| | 7. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, |
| | OTHER THAN IN THOSE LOCATIONS DESCRIBED IN PRECEDING |
| | ITEMS 5 AND 6, WHICH MEETS ALL OF THE |
| | FOLLOWING CONDITIONS: |
| | 7.1. EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 |
| | SQUARE FEET (0.84 M2); |
| | 7.2. EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457 MM) |
| | ABOVE THE FLOOR; |
| | 7.3. EXPOSED TOP EDGE GREATER THAN 36 INCHES (914 MM) |
| | ABOVE THE FLOOR; AND |
| | 7.4. ONE OR MORE WALKING SURFACE(S) WITHIN 36 INCHES |
| | (914 MM) HORIZONTALLY OF THE PLANE OF THE GLAZING. |
| | |
| | 3) SHEET A-1.0 BREAK ROOM SINK DOES NOT SHOW COMPLIANCE |
| | FOR A FRONTAL APPROACH MEETING THE FOLLOWING |
| | ACCESSIBILITY ISSUE: |
| | 2010 FBC-ACCESSIBILIITY 606; |
| | 606.1 GENERAL.. |
| | 606.2 CLEAR FLOOR SPACE. |
| | 606.3 HEIGHT. |
| | 606.4 FAUCETS. |
| | 606.5 EXPOSED PIPES AND SURFACES. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |