| Plan Review Notes For Permit 14120083 |
| Permit Number |
14120083 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-05 07:23:08 | 1. N.E.C. 210.24(D). OVERCURRENT DEVICES IN CLOTHES | | | CLOSET. | | | 2. AHU #3 O N PANEL SCHEDULE SHOWS 10KW ON MECHANICAL | | | PLAN SHOWS 5KW. | | | 3. SERVICE ENTRANCE AND FEEDER CONDUCTORS FOR 100 AMP | | | DISCONNECT AS SHOWN ON PLAN TO 8X8 WIREWAY. | | | 4. N.E.C. 210.52(C). RECEPTACLE SPACING COUNTERTOP BY 4 | | | GANG SWITCH IN KITCHEN ON REFRIGERATOR SIDE. |
|