| 2014-12-09 08:46:00 | BUILDING PLAN REVIEW |
| | PERMIT: 14120080 |
| | ADD: 1551 N FLAGLER # 907 |
| | CONT: INGELD CONTRACTORS LLC |
| | TEL: (561)215-3819 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. DEC. 09/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) REPORTS SUBMITTED FOR SAM 90 SOUND CONTROL MEET THE |
| | SOUND REQUIREMENT FOUND UNDWE SECTION 2010 FBC-B 1207.3 |
| | STRUCTURE-BORNE SOUND BUT NO REPORTS WERE SUBMITTED FOR |
| | CODE COMPLIANCE FOR FIRE AND ALLOWABLE COMBUSTIBLE |
| | MATERIALS IN TYPE I,& II CONSTRUCTION FBC-B 603.1.2 |
| | EXC. 2 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR |
| | AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | THE TEST STANDARD THIS PRODUCT SHOULD BE TESTED TO IS: |
| | |
| | 703.4.1 ELEMENTARY MATERIALS. |
| | MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| | IN ACCORDANCE WITH ASTM E 136. |
| | |
| | 703.4.2 COMPOSITE MATERIALS. |
| | MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| | MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |