Plan Review Notes
Plan Review Notes For Permit 14120080
Permit Number 14120080
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-09 08:46:00BUILDING PLAN REVIEW
 PERMIT: 14120080
 ADD: 1551 N FLAGLER # 907
 CONT: INGELD CONTRACTORS LLC
 TEL: (561)215-3819
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 09/ 2014
 ACTION: DENIED
  
 1) REPORTS SUBMITTED FOR SAM 90 SOUND CONTROL MEET THE
 SOUND REQUIREMENT FOUND UNDWE SECTION 2010 FBC-B 1207.3
 STRUCTURE-BORNE SOUND BUT NO REPORTS WERE SUBMITTED FOR
 CODE COMPLIANCE FOR FIRE AND ALLOWABLE COMBUSTIBLE
 MATERIALS IN TYPE I,& II CONSTRUCTION FBC-B 603.1.2
 EXC. 2 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 THE TEST STANDARD THIS PRODUCT SHOULD BE TESTED TO IS:
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  