| Plan Review Notes For Permit 14120052 |
| Permit Number |
14120052 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-10 08:40:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. WHEN INCLUDING THE PROPOSED RENOVATION, THE | | | CUMULATIVE LIFETIME IMPROVEMENTS FOR THIS PROPERTY | | | EXCEED 50%; THEREFORE, THIS IS CONSIDERED A | | | "SUBSTANTIAL IMPROVEMENT". | | | | | | IN ORDER TO DETERMINE THE ACTION(S) REQUIRED, IF ANY, | | | PLEASE EMAIL THE ELEVATION CERTIFICATE TO [email protected] | | | FOR PRELIMINARY REVIEW. | | | | | | WPB ADMIN CODE 94-546(B)*), FBC 2010 EXISTING BUILDING | | | 601.3 | | | | | | 2. PROVIDE DOCUMENTATION WHICH SHOWS COMPLIANCE WITH | | | FBC 2010 EXISTING BUILDING 402.5 (SHGC). | | | | | | |
|