| 2014-12-24 09:25:21 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- EQUIPMENT SIZING CALCULATIONS CAN NOT BE DONE FOR |
| | WORST CASE SCENARIO. CALCULATIONS NEED TO BE DONE FOR |
| | THE ACTUAL BUILDING ORIENTATION AS REQUIRED BY SEC. |
| | 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. REVISE AS |
| | REQUIRED. |
| | |
| | 2- PROVIDE THE SELECTED EQUIPMENT SENSIBLE AND TOTAL |
| | COOLING CAPACITIES AS REQUIRED BY SEC. 403.6.1 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | HOW OBTAINING R9.2 INSULATION ON CONCRETE WALLS AS |
| | SPECIFIED ON THE EQUIPMENT SIZING CALCULATIONS. SEC. |
| | 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 4- INFORMATION SHOWN ON THE EQUIPMENT SIZING |
| | CALCULATIONS FOR HEATING DON'T MATCH INFORMATION SHOWN |
| | ON THE ENERGY CALCULATIONS. REVISE AS REQUIRED TO |
| | MATCH. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 5- CLARIFY WHY THE EQUIPMENT SIZING CALCULATIONS ARE |
| | TAKING AN OCCUPANT LOAD OF 26 OCCUPANTS FOR THIS HOUSE. |
| | SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 6- PROVIDE THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE A/C PLAN AS REQUIRED BY SEC. |
| | 107.2.1 OF CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. |
| | |