| 2014-12-23 11:39:23 | NEW SINGLE FAMILY (R3) BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT |
| | FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION WAS UPDATED TO $180,000. THE PERMIT FEE |
| | BALANCE IS $3,518.02. SEC. 109.3 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | 3- DRAWINGS NEED THE ARCHITECT'S ORIGINAL SIGNATURE |
| | (NOT RUBBER STAMP) AS REQUIRED BY CHAPTER 481 FLORIDA |
| | STATUTE. |
| | |
| | 4- ACCORDING TO SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL THIS PROPERTY IS LOCATED IN EXPOSURE |
| | "C" NOT "B". REVISE BUILDING CODE INFORMATION ON SHEET |
| | CS-1, WINDOWS AND DOORS DESIGN PRESSURES ON SHEET |
| | A-3.0, ROOF FRAMING NOTES ON SHEET S-3.0, ETC. |
| | |
| | 5- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 6- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 7- SPECIFY ON PLANS ATTIC ACCESS. SEC. R807 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 8- NEED GUTTERS WITH DOWNSPOUTS AS REQUIRED BY SEC. |
| | R318.6 OF 2010 FBC-RESIDENTIAL. REVISE ROOF PLAN ON |
| | SHEET A-2.0 AND DETAIL 4/A-3.1. |
| | |
| | 9- REVISE DETAIL 6/A-2.0: STRUCTURAL BUCK NEED TO |
| | PROVIDE FULL SUPPORT TO THE DOOR FRAME AS REQUIRED BY |
| | SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL. DETAIL SHOWN |
| | DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME. |
| | |
| | 10- TYPICAL WALL SECTION 4/A-2.0: PROVIDE |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH THE CLEARANCE |
| | FOR TERMITE INSPECTION AS REQUIRED BY SEC. R704 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 11- PROVIDE MANUFACTURER SPECS FOR THE WINDOWS THAT |
| | SHOW THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE |
| | ENERGY CALCULATIONS ON ITEM #7. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 12- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | CONCRETE BLOCK WALL SHOWING COMPLIANCE WITH THE |
| | INSULATION R VALUE SPECIFIED ON THE ENERGY CALCULATIINS |
| | ON ITEM #9. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 13- ENERGY CALCULATIONIS SUBMITTED: |
| | A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC. |
| | 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | B) REVISE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 5. SEE |
| | PLANS AND REVISE AS REQRUIED. SEC. 103.2.1.1.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 14- SPECIFY CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| | EACH BEDROOM. THERE IS ONLY ONE CARBON MONOXIDE ALARM |
| | SHOWN ON THE HALLWAY AND IT'S MORE THAN 10 FEET AWAY |
| | FROM BEDROOMS 2 AND 5. SEC. R315 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 15- PROVIDE PRODUCT APPROVAL (2 COPIES) AS RERQUIED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SINGLE HUNG WINDOWS. NOA 12-0127.16 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. |
| | |
| | B) |
| | |
| | |
| | -PRECAST LINTELS. |
| | -STRUCTURAL CONNECTORS |
| | |
| | |
| | |
| | ***REVIEW IN PROGRESS... |