2015-03-18 13:58:41RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE A/C EQUIPMENT SIZING CALCULATIONS:
 A) CALCULATIONS NEED TO BE DONE ON THE ACTUAL
 ORIENTATION OF THE BUILDING. FRONT DOOR DOESN'T FACE
 NORTH. SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION.
 SEE PLANS AND REVISE AS REQUIRED.
  
 2- SIZE OF TRANSFER DUCTS SPECIFIED ON THE A/C PLAN FOR
 ALL BEDROOMS DON'T COMPLY WITH THE BALANCE RETURN AIR
 SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.
  