| Plan Review Notes For Permit 14120007 |
| Permit Number |
14120007 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-03-18 12:10:22 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PLANS SUBMITTED STILL SHOW ADDITIONAL BEDROOM IN THE | | | REAR STRUCTURE. ACCORDING TO PROPERTY OWNER, THERE WILL | | | BE NO ADDITIONAL BEDROOM AT THIS TIME. NEED TO REVISE | | | PLANS AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | 2- REVISE THE COMPONENTS AND CLADDING DESIGN PRESSURES | | | SHOWN ON THE DESIGN PARAMETERS ON SHEET 2 OF 3. THOSE | | | PRESSURES DON'T MEET THE DESIGN PRESSURES FOR EXPOSURE | | | "C" FOR WINDOWS/DOORS LOCATED ON THE END ZONES. REVISE | | | AS REQUIRED. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. | | | ***NOTE: PLANS WERE REVISED FOR EXPOSURE "B". THIS | | | PROPERTY IS NOT LOCATED IN EXPOSURE "B". REVISE AS | | | REQUIRED AND MAKE SURE DESIGN PRESSURES CORRESPOND TO | | | EXPOSURE "C". REVISE ORIGINAL DRAWINGS. HAND REVISONS | | | ARE NOT ACCEPTABLE. | | | | | | 3- OWNER/AGENT TO SIGN AND DATE THE ENERGY | | | CALCULATIONS. SEC. 103.2.3.2 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS.. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|