2014-12-29 17:52:49RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE A/C EQUIPMENT SIZING CALCULATIONS. SHOW THE
 MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC. 403.6
 OF 2010 FBC-ENERGY CONSERVATION.
 NOTE: SEPARATE CALCULATIONS REQUIRED FOR THE MAIN HOUSE
 AND FOR THE DETACHED BEDROOM.
  
 2- A/C PLAN TO SPECIFY ALL CFM'S AND GRILL SIZES . SEC.
 107.3.5.3(10) OF CITY AMENDMENTS TO FBC.
  
 3- A/C PLAN TO SHOW COMPLIANCE WITH THE BALANCED RETURN
 AIR AS REQUIRED BY SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. SPECIFY ALL DUCT AND GRILL SIZES.
  
 4- SPECIFY VENTILATION FOR THE BATHROOMS AS REQUIRED BY
 SEC. M1507 OF 2010 FBC-RESIDENTIAL.
  
 5- NEW DETACHED BEDROOM STRUCTURE. SHOW ON PLANS HOW
 PROVIDING HEATING TO ALL HABITABLE ROOMS AS REQUIRED BY
 SEC. R303.8 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]