| Plan Review Notes For Permit 14110952 |
| Permit Number |
14110952 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-01-20 09:31:41 | 01/20/2015 | | | PROJECT: TOWER 3 | | | PERMIT#: 14110952 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 3RD ELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION | | | | | | A SEPARATE PERMIT APPLICATION WITH SHOP DRAWINGS, | | | PRODUCT APPROVALS AND THE FOLLOWING ADDITIONAL | | | INFORMATION IS REQUIRED FOR THE INSTALLATION OF THE | | | FUTURE ELECTRICAL UTILITY RACK, GENERATOR, FUEL TANK, | | | LIGHTINING PROTECTION SYSTEM, AND EQUIPMENT SHELTER. | | | | | | 1) PROVIDE A LOAD CALCULATION, AND A RISER DIAGRAM WITH | | | A FEEDER SCHEDULE TO INDICATE THE CONDUIT, SERVICE AND | | | CONDUCTOR SIZES PROPOSED. FBC-107.3.5.3, NEC 215.5 | | | | | | 2) PROVIDE A FAULT CURRENT CALCULATION TO ENSURE THE | | | RATING OF THE PROPOSED SWITCH GEAR IS SUFFICIENT AT | | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | | INTERRUPTED. NEC 110.9 | | | | | | 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.16, 110.22 INDICATE THE REQUIRED ARC FLASH | | | PROTECTION ON EQUIPMENT. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | | | | |
|