2015-01-20 08:01:4601/20/2015
 PROJECT: TOWER 2
 PERMIT#: 14110951
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 A SEPARATE PERMIT APPLICATION WITH SHOP DRAWINGS,
 PRODUCT APPROVALS AND THE FOLLOWING ADDITIONAL
 INFORMATION IS REQUIRED FOR THE INSTALLATION OF THE
 FUTURE ELECTRICAL UTILITY RACK, GENERATOR, FUEL TANK,
 LIGHTINING PROTECTION SYSTEM, AND EQUIPMENT SHELTER.
  
 1) PROVIDE A LOAD CALCULATION, AND A RISER DIAGRAM WITH
 A FEEDER SCHEDULE TO INDICATE THE CONDUIT, SERVICE AND
 CONDUCTOR SIZES PROPOSED. FBC-107.3.5.3, NEC 215.5
  
 2) PROVIDE A FAULT CURRENT CALCULATION TO ENSURE THE
 RATING OF THE PROPOSED SWITCH GEAR IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22 INDICATE THE REQUIRED ARC FLASH
 PROTECTION ON EQUIPMENT.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  