| Plan Review Notes For Permit 14110951 |
| Permit Number |
14110951 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-12-29 11:17:57 | 12/29/2014 | | | PROJECT: TOWER 2 | | | PERMIT#: 14110951 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE A LOAD CALCULATION, AND A RISER DIAGRAM WITH | | | A FEEDER SCHEDULE TO INDICATE THE CONDUIT, SERVICE AND | | | CONDUCTOR SIZES PROPOSED. FBC-107.3.5.3, NEC 215.5 | | | | | | 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.16, 110.22 INDICATE THE REQUIRED ARC FLASH | | | PROTECTION ON EQUIPMENT. | | | | | | 3) A SEPARATE PERMIT IS REQUIRED FOR FUTURE GENERATOR, | | | FUEL TANK, AND EQUIPMENT SHELTER. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | | | | |
|