Plan Review Notes
Plan Review Notes For Permit 14110951
Permit Number 14110951
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-03 11:44:59BUILDING PLAN REVIEW
 PERMIT: 14110951
 ADD: 5801 EARNEST ST.
 CONT: SABRE COMMUNICATIONS
 TEL: (712)258-6690
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 03/ 3014
 ACTION: DENIED
  
 1) STRUCTURAL DESIGN REPORT SABRE INDUSTRIES JOB NUMBER
 : 113285 PAGE 4 NOTE # 5 INDICATES THE SOILS REPORT BY
 UNIVERSAL ENGINEERING SERVICES, PROJECT # 0630.1400040,
 SEE THE GEOTECHNICAL REPORT FOR DRILLED PIER
 INSTALATION REQUIREMENTS.
 THE SOILS REPORT FOR THE MINIMUM SAFE BEARING VALUES
 HAS NOT BEEN SUPPLIED.
  
 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 1803.5.5 DEEP FOUNDATIONS.
 WHERE DEEP FOUNDATIONS WILL BE USED, A GEOTECHNICAL
 INVESTIGATION SHALL BE CONDUCTED AND SHALL INCLUDE ALL
 OF THE FOLLOWING, UNLESS SUFFICIENT DATA UPON WHICH TO
 BASE THE DESIGN AND INSTALLATION IS OTHERWISE
 AVAILABLE:
 1. RECOMMENDED DEEP FOUNDATION TYPES AND INSTALLED
 CAPACITIES.
 2. RECOMMENDED CENTER-TO-CENTER SPACING OF DEEP
 FOUNDATION ELEMENTS.
 3. DRIVING CRITERIA.
 4. INSTALLATION PROCEDURES.
 5. FIELD INSPECTION AND REPORTING PROCEDURES (TO
 INCLUDE PROCEDURES FOR VERIFICATION OF THE INSTALLED
 BEARING CAPACITY WHERE REQUIRED).
 6. LOAD TEST REQUIREMENTS.
 7. SUITABILITY OF DEEP FOUNDATION MATERIALS FOR THE
 INTENDED ENVIRONMENT.
 8. DESIGNATION OF BEARING STRATUM OR STRATA.
 9. REDUCTIONS FOR GROUP ACTION, WHERE NECESSARY.
  
 2) PEASE SHOW COMPLIANCE WITH: 1810.3.9 CAST-IN-PLACE
 DEEP FOUNDATIONS.
 CAST-IN-PLACE DEEP FOUNDATION ELEMENTS SHALL BE
 DESIGNED AND DETAILED IN ACCORDANCE WITH SECTIONS
 1810.3.9.1 THROUGH 1810.3.9.6.
 1810.3.9.1 DESIGN CRACKING MOMENT.
 THE DESIGN CRACKING MOMENT (FMN) FOR A CAST-IN-PLACE
 DEEP FOUNDATION ELEMENT NOT ENCLOSED BY A STRUCTURAL
 STEEL PIPE OR TUBE SHALL BE DETERMINED USING THE
 FOLLOWING EQUATION:
  (EQUATION 18-11) SEE FBC-B CODE BOOK.
 WHERE:
 F ' C = SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE OR
 GROUT, PSI (MPA).
 SM = ELASTIC SECTION MODULUS, NEGLECTING REINFORCEMENT
 AND CASING, CUBIC INCHES (MM3).
  
 3) PLANS SUBMITTED BY CHAD E. TUTTLE P. E. / LICENSE #
 57199 THE COPIED SEAL MEASURES APPROXIMATELY 3 3/4
 INCHES IN DIAMETER.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001 SEALS
 ACCEPTABLE TO THE BOARD. SAID SEAL SHALL BE A MINIMUM
 OF 1 7/8 INCHES IN DIAMETER, TO SAY LICENSE NOT
 CERTIFICATE. ALL ENGINEERS MUST BE UTILIZING SAID SEAL
 NO LATER THAN JANUARY 1, 2006.
  
 4) PLANS SUBMITTED BY CHAD E. TUTTLE P. E. / LICENSE #
 57199 THE SIGNATURE IS PHOTOCOPIED, YOU CAN SEE THE
 PIXELS IN THE PRINT, NOT SIGNED A WET SIGNATURE.
 FLORIDA ADMINISTRATIVE CODE PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL
 HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL
 AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS EFFECTIVE DATE
 05/06/2009
 (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
  
 5) SHEET C-2 & C-5 INDICATES GENERATOR, FUEL TANK AND
 WHAT APPEARS TO BE A MANUFACTURERED BUILDING 11'-5" X
 20'-0" , NO PLANS WERE SUBMITTED A SEPARATE REVIEW AND
 PERMIT WILL BE REQUIRED FOR EACH STRUCTURE.
  
 6) THE STRUCTURAL DESIGN REPORT LIST PAGE # 8 FOR THE
 MAXIMUM GUY TENSIONS, ANCHOR LOADS AND BASE LOADS,
 SHEET C-6 OF PLANS SHOWS SOME ANCHOR DETAILS, PLEASE
 PROVIDE HOW THE GUY WIRE WILL BE ANCHORED INTO THE
 FOUNDATION, SIZE OF CABLE AND ANCHORING SYSTEM FROM GUY
 WIRE TO FOUNDATION. THIS IS PART OF THE MWFRS, MAIN
 WIND FORCE RESISTING SYSTEM.
  
 7) PLEASE PROVIDE WHERE THE TRIANGULAR OR SQUARE
 LATTICED TOWER DIRECTIONAL FACTOR OF 0.85 CAN BE FOUND
 , IT IS NOT IN THE STRUCTURAL NOTES AND DESIGN FACTORS
 FOUND ON PAGE 01. ANSI/ EIA/TIA- 222G- 05.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  