Plan Review Notes
Plan Review Notes For Permit 14110950
Permit Number 14110950
Review Stop E
Sequence Number 2
Notes
Date Text
2014-12-29 12:59:5812/29/2014
 PROJECT: TOWER 1
 PERMIT#: 14110950
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) PROVIDE A LOAD CALCULATION, AND A RISER DIAGRAM WITH
 A FEEDER SCHEDULE TO INDICATE THE CONDUIT, SERVICE AND
 CONDUCTOR SIZES FOR FUTURE EQUIPMENT SHELTER.
 FBC-107.3.5.3, NEC 215.5
  
 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22 INDICATE THE REQUIRED ARC FLASH
 PROTECTION ON FUTER ELECTRICAL EQUIPMENT.
  
 3) A SEPARATE PERMIT IS REQUIRED FOR THE FUTURE
 GENERATOR, FUEL TANK, AND EQUIPMENT SHELTER.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved