| | PROJECT: TOWER 1 |
| | PERMIT#: 14110950 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A LOAD CALCULATION AND PANEL SCHEDULES TO |
| | INDICATE THE TOTAL CONNECTED LOAD AND CIRCUITRY |
| | INVOLVED IN THE SCOPE OF THIS PROJECT. IDENTIFY CIRCUIT |
| | NUMBERS ON PLAN. FBC- 107.3.5.3 |
| | |
| | 2) PROVIDE CLARIFICATION FOR THE FOLLOWING: FBC-107.3.5 |
| | SHEET E-1 INDICATES CONDUIT ROUTING FOR TELCO AND POWER |
| | FROM THE EXISTING EQUIPMENT SHELTER TO THE NEW |
| | EQUIPMENT SHELTER BUT HAVE CONFLICTING DETAILS IN #3 |
| | ?SERVICE UTILITY TRENCH? AND #4 ?TRENCH DETAIL? |
| | SHEET E-2 INDICATES A PROPOSED MULTI-TENANT RACK WITH |
| | MULTIPLE METER SOCKETS AND DISCONNECTS BUT NO SPECIFIC |
| | LOCATION. INDICATE THE LOCATION OF THE MULTI-TENANT |
| | RACK. |
| | SHEET E-3 INDICATES A BASIC ONE LINE DIAGRAM WITH |
| | METER, DISCONNECT AND TRANSFER SWITCH AND PANEL N WITH |
| | NO SPECIFIC LOCATION. INDICATE THE LOCATION OF THE |
| | ELECTRICAL SERVICE AND PANEL N |
| | SHEET C-5 INDICATES A SINGLE DISCONNECT AND GENERATOR |
| | INTERFACE PANEL ON THE NEW EQUIPMENT ENCLOSURE WITH NO |
| | METER AND NO PANEL N?. CLARIFICATION REQUIRED. |
| | |
| | 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 INDICATE THE REQUIRED ARC FLASH |
| | PROTECTION ON EQUIPMENT. |
| | |
| | 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. F.S. 471, WPB |
| | AMENDMENTS TO FBC 107.2.1 |
| | |
| | 5) A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR, AND |
| | RELATED EQUIPMENT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |