 PROJECT: TOWER 1
 PERMIT#: 14110950
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A LOAD CALCULATION AND PANEL SCHEDULES TO
 INDICATE THE TOTAL CONNECTED LOAD AND CIRCUITRY
 INVOLVED IN THE SCOPE OF THIS PROJECT. IDENTIFY CIRCUIT
 NUMBERS ON PLAN. FBC- 107.3.5.3
  
 2) PROVIDE CLARIFICATION FOR THE FOLLOWING: FBC-107.3.5
 SHEET E-1 INDICATES CONDUIT ROUTING FOR TELCO AND POWER
 FROM THE EXISTING EQUIPMENT SHELTER TO THE NEW
 EQUIPMENT SHELTER BUT HAVE CONFLICTING DETAILS IN #3
 ?SERVICE UTILITY TRENCH? AND #4 ?TRENCH DETAIL?
 SHEET E-2 INDICATES A PROPOSED MULTI-TENANT RACK WITH
 MULTIPLE METER SOCKETS AND DISCONNECTS BUT NO SPECIFIC
 LOCATION. INDICATE THE LOCATION OF THE MULTI-TENANT
 RACK.
 SHEET E-3 INDICATES A BASIC ONE LINE DIAGRAM WITH
 METER, DISCONNECT AND TRANSFER SWITCH AND PANEL N WITH
 NO SPECIFIC LOCATION. INDICATE THE LOCATION OF THE
 ELECTRICAL SERVICE AND PANEL N
 SHEET C-5 INDICATES A SINGLE DISCONNECT AND GENERATOR
 INTERFACE PANEL ON THE NEW EQUIPMENT ENCLOSURE WITH NO
 METER AND NO PANEL N?. CLARIFICATION REQUIRED.
  
 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22 INDICATE THE REQUIRED ARC FLASH
 PROTECTION ON EQUIPMENT.
  
 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. F.S. 471, WPB
 AMENDMENTS TO FBC 107.2.1
  
 5) A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR, AND
 RELATED EQUIPMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  