| Plan Review Notes For Permit 14110936 |
| Permit Number |
14110936 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-10 09:27:09 | BUILDING PROVISO | | | THE ELEVATOR ENCLOSURE IS LOCATED IN A SPECIAL FLOOD | | | HAZARD AREA (A5 FLOOD ZONE ) AND IS REQUIRED TO COMPLY | | | WITH FBC-R322 AND ASCE 24-05. THEREFORE, THE FOLLOWING | | | ARE ITEMS ARE REQUIRED: | | | 1) THE ENCLOSURE IS REQUIRED TO BE DESIGNED TO RESIST | | | FLOOD LOADS (I.E., HYDROSTATIC, HYDRODYNAMIC, | | | FLOOD-BORNE DEBRIS, EROSION AND SCOUR). PROVIDE A | | | LETTER OF AFFIRMATION FROM THE ENGINEER. | | | 2) THE ELEVATOR EQUIPMENT SHALL BE LOCATED ABOVE THE | | | 7.5' BASE FLOOD ELEVATION. IF EQUIPMENT MUST BE LOCATED | | | BELOW THE BFE, IT SHALL BE PROTECTED USING FLOOD | | | DAMAGE-RESISTANT COMPONENTS. | | | 3) THE ELEVATOR CAB MUST BE EQUIPPED WITH CONTROLS THAT | | | PREVENT THE CAB FROM DESCENDING INTO FLOOD-WATERS. |
|