Plan Review Notes
Plan Review Notes For Permit 14110935
Permit Number 14110935
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-15 08:33:4712/15/2014
 PROJECT: 285 BARCELONA
 PERMIT#: 14080586
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW FOR REVISION TRACKING#14110935
 ACTION: DENIED.
  
 1) E-1
 REVISE NOTES: THERE ARE A COUPLE OF SMALL NOTES AT THE
 BOTTOM OF THE SYMBOLS LEGEND NEXT TO THE RECESSED
 LIGHTS AND SMOKE DETECTOR SYMBOLS AND THEN THERE ARE A
 FEW LARGER NOTES ON THE TOP CENTER OF THE SHEET.
 COMBINE ALL NOTES FOR CLARITY AND ADD:
 A.) ALL NEW 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. (1)BATHROOMS, (2)GARAGES, (3)OUTDOORS,
 (4)CRAWL SPACES, (5)UNFINISHED BASEMENTS, (6)KITCHES,
 (6)LAUNDRY ROOMS, (7)AND (8)BOATHOUSES. NEC 210.8
 B.) ALL LUMINAIRES IN CLOTHES CLOSETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC
 410.16(A) AND (B).
  
 2) E-2
 REVISE RISER DIAGRAM TO TO INCLUDE WIRE AND CONDUIT
 SIZES AND TYPE BETWEEN METER AND MAIN DISCONNECT, AND
 BETWEEN THE GUTTER AND PANEL B.
  
 AN ELECTRICAL APPLICATION IS REQUIRED FOR THIS SCOPE.
 NONE ON FILE AT THIS TIME.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  