| 2014-12-15 08:33:47 | 12/15/2014 |
| | PROJECT: 285 BARCELONA |
| | PERMIT#: 14080586 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | ELECTRICAL PLAN REVIEW FOR REVISION TRACKING#14110935 |
| | ACTION: DENIED. |
| | |
| | 1) E-1 |
| | REVISE NOTES: THERE ARE A COUPLE OF SMALL NOTES AT THE |
| | BOTTOM OF THE SYMBOLS LEGEND NEXT TO THE RECESSED |
| | LIGHTS AND SMOKE DETECTOR SYMBOLS AND THEN THERE ARE A |
| | FEW LARGER NOTES ON THE TOP CENTER OF THE SHEET. |
| | COMBINE ALL NOTES FOR CLARITY AND ADD: |
| | A.) ALL NEW 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| | FOR PERSONNEL. (1)BATHROOMS, (2)GARAGES, (3)OUTDOORS, |
| | (4)CRAWL SPACES, (5)UNFINISHED BASEMENTS, (6)KITCHES, |
| | (6)LAUNDRY ROOMS, (7)AND (8)BOATHOUSES. NEC 210.8 |
| | B.) ALL LUMINAIRES IN CLOTHES CLOSETS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC |
| | 410.16(A) AND (B). |
| | |
| | 2) E-2 |
| | REVISE RISER DIAGRAM TO TO INCLUDE WIRE AND CONDUIT |
| | SIZES AND TYPE BETWEEN METER AND MAIN DISCONNECT, AND |
| | BETWEEN THE GUTTER AND PANEL B. |
| | |
| | AN ELECTRICAL APPLICATION IS REQUIRED FOR THIS SCOPE. |
| | NONE ON FILE AT THIS TIME. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |