| Plan Review Notes For Permit 14110924 |
| Permit Number |
14110924 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-26 05:47:56 | 1) SUBMIT 2 COPIES OF MANUF. SPECIFICATION SHEETS FOR | | | ALL GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND | | | LABELED PER SEC. 301.3 OF THE 2010 FL. GAS CODE. | | | 2) SHOW ALL THE TYPES OF PIPE MATERIAL BEING INSTALLED. | | | ALL PIPE SIZES AND THE CORRESPONDING EHD NUMBER OF | | | CORRUGATED STAINLESS STELL TUBING FOR EACH PIPE SIZE IF | | | BEING USED. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 3)SHOW THE BTU LOAD OF EACH APPLIANCE ON THE SYSTEM | | | INCLUDING EXISTING APPLIANCES AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. FGC SECS. 401.8 THRU 402.6.1. AND TABLES | | | 402.4 (1) THRU 402.4 (35) | | | 4) SHOW THE TOTAL DISTANCE FROM THE POINT OF DELIVERY ( | | | METER OR MP REGULATOR) TO THE MOST REMOTE OUTLETON THE | | | SYSTEM. FGC SEC.402.4.1. | | | 5)INDICATE THE DELIVERY PRESSURE FOR THE SYSTEM. THE | | | DRAWING SHOWS 2 PSI AT ONE POINT. WHAT ABOUT THE REST | | | OF THE SYSTEM? | | | 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR. 2010 FGC | | | SEC.304. | | | 7) SUBMIT 2 COPIES OF THE APPLICABLE GAS SIZING TABLES | | | FROM THE 2010 FGC. | | | 8) SHOW THE LOCATION OF ALL MEDIUM PRESSURE (MP) | | | REGULATORS AND 2ND STAGE REGULATORS.WPB AMEND. TO 2010 | | | FBC SEC. 107.2.1. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|