| 2014-12-16 16:28:44 | 12/16/2014 |
| | PROJECT: TANNING SALON |
| | PERMIT#: 14110915 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) REVISE THE RISER DIAGRAM TO INDICATE THE SIZE OF THE |
| | EXISTING FEEDERS TO PANEL A AND PANEL B. NEC 215.5 |
| | |
| | 2) PROVIDE A SITE PLAN THAT INCLUDES THE LOCATION OF |
| | BAY#2505, THE LOCATION OF THE EXISTING SERVICE AND THE |
| | LOCATION OF THE NEW SERVICE TO SHOW COMPLIANCE WITH THE |
| | NEC 230.72 "GROUPING OF DISCONNECTS," |
| | |
| | 3) INDICATE THE ROUTING OF THE NEW SERVICE FEEDER TO |
| | INDICATE COMPLIANCE WITH NEC 230.3 "ONE BUILDING OR |
| | OTHER STRUCTURE NOT TO BE SUPPLIED THROUGH ANOTHER." |
| | |
| | 4) PROVIDE REASONING FOR THE NEW SERVICE TO INDICATE |
| | COMPLIANCE WITH NEC 230.2 " NUMBER OF SERVICES" . |
| | |
| | 5) PROVIDE A COMPLETE LOAD CALCULATION OF THE |
| | ELECTRICAL SERVICE INCLUDING THE EXISTING AND NEW |
| | PANELS INDICATING THE TOTAL CONNECTED LOAD AFTER THE |
| | ADDITION OF NEW CIRCUITS. BASED ON PART II AND III OF |
| | THE NEC 220 |
| | |
| | 6) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 7) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | |
| | 8) PROVIDE MANUFACTURER PRODUCT SPECIFICATIONS |
| | INDICATING THE NRTL LISTING, VOLTAGE AND KW LOAD FOR |
| | EACH PEICE OF EQUIPMENT. NEC 110.3(B) |
| | |
| | 9) REVISE THE PLANS TO CLARIFY GROUNDING OF THE BUCK |
| | BOOST TRANSFORMERS. PROVIDE A DETAIL INDICATING HOW TO |
| | CONNECT THE BUCK BOOST TRANSFORMER'S GROUNDING |
| | ELECTRODE BACK TO THE MAIN GROUNDING ELECTRODE SYSTEM |
| | VIA EQUIPMENT GROUND SIZED IN ACCORDANCE WITH THE NEC |
| | 250.122 |
| | |
| | 10) REVISE THE FLOOR PLAN TO INDICATE THE LOCATIONS OF |
| | THE BUCK BOOST TRANSFORMER WHERE REQUIRED. FBC-WPB |
| | AMENDMENTS 107.3.5 |
| | |
| | 11) REVISE THE PLAN TO INDICATE THE REQUIRED CLEARANCE |
| | AND DEDICATED WORKING SPACE ABOUT ELECTRICAL EQUIPMENT |
| | INCLUDING THE SERVICE EQUIPMENT, SERVICE PANELS, BUCK |
| | BOOST TRANSFORMERS AND DISCONNECTS FOR TANNING |
| | EQUIPMENT. NEC110.26 |
| | |
| | 12) REVISE THE PLAN TO INDIACTE THE LOCATION OF THE |
| | LIGHTING CONTACTOR(S) AND PROVIDE ADDITIONAL DETAIL TO |
| | INDICATE COMPLIANCE WITH FBC-E 505.2 LIGHTING CONTROLS |
| | (MANDATORY) LIGHTING SYSTEMS SHALL BE PROVIDED WITH |
| | CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2, |
| | 505.2.3 AND 505.2.4. |
| | |
| | 13) THE BRANCH CIRCUIT FEEDING THE EXIT AND EMERGENCY |
| | LIGHTING EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS |
| | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 700.12(F) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |