| Plan Review Notes For Permit 14110892 |
| Permit Number |
14110892 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-04 13:17:20 | 1) SHT. A-3 - DETAIL #4 - THE DOWNSPOUT FOR THE ROOF | | | DRAINAGE SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM THE | | | BUILDING WALL PER THE 2010 FLORIDA BUILDING CODE | | | SEC.1503.7. | | | 2) SUBMIT A RISER DIAGRAM FOR THE STORM DRAIN | | | COLLECTION SYSTEM. INDICATE ALL PIPE SIZES AND THE | | | SQUARE FOOTAGE OF THE ROOF THAT IS DRAINED BY EACH | | | INDIVIDUAL ROOF DRAIN.INCLUDE 1/2 OF THE AREA OF THE | | | PARAPET WALL TO THE PROJECTED ROOF AREA CALCULATIONS. | | | WPB AMEND. TO 2010 FBC SEC.107.3.5.1.3. | | | 3) SHT.A-7 - ROOF PLAN - THERE IS A NOTE AT ONE OF THE | | | ROOF DRAINS ON THE EXISTING ROOF THAT STATES "SEE NOTE | | | 10." THERE IS NO NOTE 10 ON THIS PGE.CLARIFY. | | | 4) THE PVC ON THE ROOF SHALL BE PROTECTED FROM UV RAYS | | | PER MANUF. RECOMMENDATIONS AND ASTM REQS, FPC 303.2.. | | | 5) SHT.P-1 - INDICATE THE SIZE OF THE DRAIN FROM THE | | | NFHB ON THE ROOF. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|