| 2014-12-15 14:03:19 | 12/15/2014 |
| | PROJECT: AUTOZONE 1261 |
| | PERMIT#: 14110892 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) REVISE RISER DIAGRAM WITH REPECT TO THE FOLLOWING: |
| | A) THE SERVICE ENTRANCE CONDUCTOR SET IS INDICATED AS |
| | TWO SETS OF 4, 250MCM ON THE LINE SIDE COMING IN AND |
| | THE AFTER THE CT'S IS INDICATED AS TWO SETS OF 4, 3/0. |
| | THIS IS CONFLICTING. DETERMINE THE ACTUAL METERING |
| | MEATHOD AND INDICATE THIS ACCUARATELY ON THE PLAN. |
| | |
| | 2) INDICATE LOCATION FOR ALL PANELS AND IDENTIFY EACH |
| | ON THE FLOOR PLAN. |
| | |
| | 3) PROVIDE A SIGN CIRCUIT NEC 600.5. INDICATE THE SIGN |
| | CIRCUIT ON THE PANEL SCHEDULE AND INDICATE COMPLIANCE |
| | WITH THE FBC-E 505.2 |
| | |
| | 4) INDICATE COMPLIANCE WITH THE FBC-E 505.2. LIGHTING |
| | SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN |
| | SECTIONS 505.2.1, 505.2.2, 505.2.3 AND 505.2.4. PROVIDE |
| | SCHEDULE AND CONTROL DETAIL FOR LIGHTING CONTACTOR(S) |
| | |
| | 5) IDENTIFY ALL SYMBOLS, AND CIRCUITS ON FLOOR PLAN. |
| | ALL SYMBOLS TO COINCIDE WITH SYMBOLS LEGEND AND ALL |
| | CIRCUITS TO COINCIDE WITH PANEL SCEDULE(S). |
| | |
| | 6) PROVIDE ALL PANEL SCHEDULES. |
| | |
| | 7) A SEPARATE GROUND ROD AS PROPOSED MUST BE CONNECTED |
| | TO THE ELECTRICAL GROUNDING ELECTRODE SYSTEM TO AVOID |
| | ANY DIFFERENCE OF POTENTIAL. |
| | |
| | 8) DRINK MACHINE OUTLET TO BE GFI PROTECTED. NEC 422.51 |
| | |
| | 9) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. NEC 700.12(F) |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD |
| | EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, |
| | CCTV, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |