| Plan Review Notes For Permit 14110863 |
| Permit Number |
14110863 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-28 07:20:27 | 1) THE DOOR IN THE WOMEN'S AND MEN'S RESTROOM APPEARS | | | TO BE SWINGING INTO THE CLEAR FLOOR SPACE REQUIRED FOR | | | THE WATER CLOSET AND TOILET. COMPLY W/2010 FL. | | | ACCESSIBILITY CODE SEC.603.2.3. | | | 2) A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQUIRED PER | | | THE FAC SEC.211.2. | | | 3) SHT. A6.00 - TYPICAL RESTROOM DETAIL SHOWS THE DOORS | | | SWINGING OUT AND THE ARCHITECTURAL MAND MEP PLANS SHOW | | | THE DOORS SWINGING IN. CLARIFY. | | | 4) AN EMERGENCY EYE WASH SHALL BE INSTALLED IN THE | | | WAREHOUSE AREA PER FPC TABLE 403.1. | | | 5) THE BREAK ROOM SHALL BE INCLUDED IN THE OCCUPANT | | | LOAD CALCULATION AS THIS IS AN OCCUPIABLE AREA PER THE | | | FBC SEC.202. | | | 6) SUBMIT MANUF, SPEC/INSTALLATION INSTRUCTIONS FOR THE | | | INSTANTANEOUS WATER HEATER. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1. | | | 7) SHT. P2 - NOTE #1 STATES "REFER TO CIVIL FOR | | | CONTINUATION" BUT THERE ARE NO CIVIL DRAWINGS IN THE | | | PLAN SET. CLARIFY. | | | 8) A BACKFLOW PREVENTER SHALL BE PLACED AT THE METER | | | PER CITY ORDINANCE SEC. 90-33 AND THE CITY'S CROSS | | | CONNECTION MANUAL. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|