| Plan Review Notes For Permit 14110854 |
| Permit Number |
14110854 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-03 11:08:41 | PLAN DENIED | | | 1) REFER TO SECTION 304.1 GENERAL AND | | | 606.2.1 SUPPLY AIR SYSTEMS FBC (M) 2010 | | | FOR RTU 1,2,3,4 AND 8 | | | 2) SHOW TERMINATION OF ALL EXHAUST REFER TO | | | SECTION501.2 EXHAUST DISCHARGE 2010 FBC (M) | | | 3) PROVIDE A DETAIL FROM THE ENGINEER FOR | | | CURB TO ROOF TIE DOWN AND RTU TO CURB TIE DOWN | | | 301.12 WIND RESISTANCE | | | 4) REFER TO SECTION 1509.7 MECHANICAL UNITS | | | 2010 FBC | | | 5) DRYER BOOSTER FANS ARE NOT PERMITTED IN THE | | | CITY OF WEST PALM BEACH PER FIRE DEPARTMENT. | | | 6) REFER TO SECTION 601.4 BALANCED RETURN AIR | | | 2010 FBC (M) | | | 7) REFER TO SECTION 603.5 NONMETALLIC DUCT | | | 2010 FBC (M). | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|