| 2014-12-03 13:17:51 | 5335 NORTH MILITARY TRAIL #19 |
| | PERMIT #14110854 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| | (2009 EDITION WITH FLORIDA AMENDMENTS.) |
| | |
| | SHEET T1.0: CODE SECTION INCORRECTLY REFERENCES CHAPTER |
| | 36 (NEW MERCANTILE) IN LIEU OF CHAPTER 12 (NEW |
| | ASSEMBLY) OF THE LIFE SAFETY CODE. |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING ALL |
| | CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING, "FIRE |
| | PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING |
| | (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE |
| | FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY." |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | SHEET A1.0: INDICATE THE EXISTING OCCUPANCY TYPES FOR |
| | THE TENANTS LOCATED ON BOTH SIDES OF THE NEW ASSEMBLY |
| | OCCUPANCY. INDICATE IF THE TENANT SEPARATION WALL HAS A |
| | FIRE RATED BARRIER. |
| | |
| | SHEET A1.0: PER SECTION12.3.2.1.2, LAUNDRY AREAS |
| | (JANITOR #110) SHALL BE SEPARATED FROM ADJACENT AREAS |
| | WITH A 1-HOUR FIRE BARRIER AND AUTOMATIC SPRINKLERS. |
| | PROTECT ALL OPENINGS AND PENETRATIONS. PROVIDE FIRE |
| | DAMPERS FOR DUCTWORK (SHEET M1.0). |
| | |
| | SHEET A1.2: RUBBER FLOORING - PER SECTION 10.2.7.2, |
| | FLOOR COVERINGS, OTHER THAN CARPET, SHALL HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | SHEET A3.0: NO OTHER LOCKS OR LATCHES ARE PERMITTED |
| | THAT WOULD NOT BE RELEASED BY THE PANIC HARDWARE. AS A |
| | SUBSTITUTE FOR PANIC HARDWARE, THE MAIN ENTRANCE IS |
| | PERMITTED TO HAVE AN INTERIOR KEYED DOOR LOCK (AND NO |
| | LATCH) WITH A READILY VISIBLE SIGN STATING THIS DOOR TO |
| | REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN |
| | LETTERS SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK |
| | TO BE EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW |
| | (SUCH AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN |
| | STYLE LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A |
| | KEYED LOCK. |
| | |
| | GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED |
| | SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED |
| | IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE |
| | ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | SHEET E1.1 & SHEET A2.0: ARCHITECT SHOWS FIRE ALARM |
| | DEVICES FOR REFERENCE ONLY. PROVIDE VISUAL NOTIFICATION |
| | COVERAGE IN ALL PUBLIC AND COMMON USE SPACES SUCH AS |
| | TANNING AND MASSAGE. FIRE ALARM NOTIFICATION LACKING IN |
| | WORKOUT #101. A CERTIFICATE OF COMPLETION AND A THIRD |
| | PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE |
| | SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM |
| | INSPECTION. |
| | |
| | FIRE SPRINKLER DESIGN/MODIFICATION: FOR ISSUANCE OF A |
| | GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE |
| | FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| | 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | NOTE - FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| | VIOLATIONS OF THIS CODE. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |