| 2015-01-08 13:53:23 | |
| | 14110854 |
| | 5335 N. MILITARY TRAIL #19 |
| | PLANET FITNESS |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. ALL COMMENTS BASED ON THE 2008 NEC. |
| | |
| | PROVIDE AN ELECTRICAL RISER PLAN FOR THE ELECTRICAL |
| | SERVICE FEEDING THIS BUILDING SHOWING LOCATION OF ALL |
| | METERS AND MAIN DISCONNECTS. VERIFY THE ELECTRICAL |
| | SERVICE MAINS SERVING THIS BUILDING INCLUDING UNIT #19 |
| | ARE SIX OR LESS AND GROUPED IN ONE LOCATION. INDICATE |
| | THE REQUIRED FAULT CURRENT RATING FOR ALL NEW |
| | EQUIPMENT. NEC 110.9, 110.10, 215.5, 230.71, |
| | |
| | THE MINIMUM SIZE EQUIPMENT GROUNDING CONDUCTOR FOR 1200 |
| | AMPERE IS 3/0. VERIFY THE INTENDED USE AND PROPOSED |
| | TERMINATION POINT FOR THE 2/0 EQUIPMENT GROUND ROUTED |
| | WITH THE SERVICE CONDUCTORS. NEC T. 250.122 |
| | |
| | INDICATE THE SIZE AND TYPE OF GROUNDING ELECTRODE |
| | PROPOSED FOR THIS SERVICE. NEC 250.32, 250.52 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING |
| | MEANS. NEC 110.22 |
| | |
| | PROVIDE DEDICATED SPACE FOR THE ELECTRICAL DISCONNECTS |
| | AND PANEL BOARDS. NEC 110.26, 240.24(D) |
| | |
| | ON THE PANEL SCHEDULE INCLUDE THE SHOW WINDOW LIGHTING |
| | AND SIGN CIRCUIT. PROVIDE SHOW WINDOW LIGHTING OUTLETS. |
| | NEC 210.62, 408.4, 600.5 |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN |
| | WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; |
| | 505.5.3; T. 505.5.3 |
| | |
| | PROVIDE A STRUCTURAL DETAIL FOR HANGING THE TWO LARGE |
| | CEILING FANS. FBC 1604.1 |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM |
| | SYSTEMS, SECURITY AND DATA SYSTEMS. |
| | |
| | |
| | ROBERT LECKY, CBO |
| | ELECTRICAL PLANS REVIEW |
| | 561-373-3701 |
| | [email protected] |
| | |