| Date |
Text |
| 2014-12-09 15:17:01 | BUILDING PLAN REVIEW |
| | PERMIT: 14110854 |
| | ADD: 5335 N. MILITARY TRAIL |
| | CONT: TO BE DETERMINED |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. DEC. 09/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) BOTH SHEETS EG1.0 & A1.0 BOTH INDICATE THE TENANT |
| | SEPARATION WALL TO BE A 1 HOUR TENANT SEPARATION WALL. |
| | THE PLANS FAIL TO IDENTIFY WHAT TYPE OF OCCUPANCY IS ON |
| | BOTH SIDES OF THE A3 OCCUPANCY. 2010 FBC-B TABLE 508.4 |
| | |
| | 2) THE COVERSHEET T.1.0 INDICATES THIS SPACE TO BE FIRE |
| | SPRINKLERED, BUT NO PLANS WERE SUBMITTED. UNDER THE |
| | 2010 FBC-B TABLE 508.2.5 INCIDENTAL ACCESSORY |
| | OCCUPANCIES LAUNDRY ROOMS OVER 100 SQ. FT. HAVE TO BE |
| | EITHER 1 HOUR FIRE RATED OR FIRE SPRINKLERED. TO TAKE |
| | THE CREDIT THE CODE GIVES FOR FIRE SPRINKLERS PLANS |
| | HAVE TO BE SUBMITTED. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: (5.) FIRE SUPPRESSION |
| | SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE SPRINKLERS |
| | |
| | 3) SHEET A1.0 INDICATES IN THE LOCKER ROOMS ACCESSIBLE |
| | LOCKERS, SHEET A5.0 SHOWS DETAILS FOR ACCESSIBLE |
| | BENCHES, THEY ARE MISSING ON THE A1.0 LOCKER ROOM |
| | DETAILS. SEE 2010 FBC-ACCESSIBILITY CODE 903.1-4 . |
| | |
| | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |