| Plan Review Notes For Permit 14110845 |
| Permit Number |
14110845 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-12-28 12:25:44 | RESIDENTIAL (R3) ADDITION, FOURTH BUILDING REVIEW | | | CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1-PROVIDE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE | | | WITH THE NEW ROOF CROSS VENTILATION AS REQUIRED BY SEC. | | | R806 OF 2010 FBC-RESIDENTIAL. (REPEAT COMMENT). | | | RESPONSE: | | | ENGINEER STATED ON TYPICAL WALL SECTION ON SHEET S-300 | | | THAT "ATTIC TO BE UNVENTED SPACE AS PER FBC-RESIDENTIAL | | | SECTION 806.4". SPECIFICATIONS SHOWN ON THE TYPICAL | | | WALL SECTION DON'T COMPLY WITH SEC. R806.4 FOR AN | | | UNVENTED ATTIC ASSEMBLY. THE LOCATION OF THE INSULATION | | | IS INCORRECT. SEE SEC. R806.4 AND REVISE AS REQUIRED. | | | AND, CLEARLY SPECIFY WHICH OPTION OF ITEM #4 OF SEC. | | | R806.4 IS GOING TO BE INSTALLED. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPPLE OLD | | | COPY TO PLANS. SUBMITT OLD COPIES FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|