2015-12-28 12:25:44RESIDENTIAL (R3) ADDITION, FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1-PROVIDE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE NEW ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806 OF 2010 FBC-RESIDENTIAL. (REPEAT COMMENT).
 RESPONSE:
 ENGINEER STATED ON TYPICAL WALL SECTION ON SHEET S-300
 THAT "ATTIC TO BE UNVENTED SPACE AS PER FBC-RESIDENTIAL
 SECTION 806.4". SPECIFICATIONS SHOWN ON THE TYPICAL
 WALL SECTION DON'T COMPLY WITH SEC. R806.4 FOR AN
 UNVENTED ATTIC ASSEMBLY. THE LOCATION OF THE INSULATION
 IS INCORRECT. SEE SEC. R806.4 AND REVISE AS REQUIRED.
 AND, CLEARLY SPECIFY WHICH OPTION OF ITEM #4 OF SEC.
 R806.4 IS GOING TO BE INSTALLED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPPLE OLD
 COPY TO PLANS. SUBMITT OLD COPIES FOR REFERENCE.
  