| Plan Review Notes For Permit 14110845 |
| Permit Number |
14110845 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-08-27 15:55:40 | 1ST REVIEW: FBC 2010 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | 561-805-6711 | | | [email protected] | | | | | | COMMENTS: | | | 1. SUBMIT CALCULATIONS FOR ROOF SCUPPERS AND | | | DOWNSPOUTS. | | | PER WPB AMEND. SEC 107.2.1.3 | | | 2.SUBMIT WATER PIPE RISER DIAGRAM. | | | PER WPB AMEND. SEC107.3.5.3(11) | | | 3.SUPPLY SPECS FOR TANKLESS WATER HEATER. | | | PER WPB AMEND. SEC 107.2.1.3 | | | 4.SEPARATE PERMIT MUST BE PULLED BY LICENSED CONTRACTOR | | | FOR GAS. | | | PER WPB AMEND. 105.1 | | | | | 2015-08-24 11:23:13 | NEW DRAWINGS SUBMITTED. SEE ALSO REVISED SHEET E-1. JG. |
|