Plan Review Notes
Plan Review Notes For Permit 14110845
Permit Number 14110845
Review Stop M
Sequence Number 2
Notes
Date Text
2015-08-25 08:58:18RESIDENTIAL (R3) ADDITION SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PERSON RESPONSIBLE FOR THE M.1 DRAWING TO PROVIDE
 NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC. (REPEAT COMMENT. NOT ADDRESSED).
  
 2- A) EQUIPMENT INFORMATION IS NOT CLEAR. DRAWINGS S-1
 AND E-1 SHOW ONE A/C UNIT. DRAWING M.1 SUBMITTED SHOWS
 TWO A/C UNITS. COORDINATE ALL PLANS AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS. (REPEAT COMMENT.
 MECHANICAL PLAN AND ENGINEER'S PLANS DON'T MATCH.
 INFORMATION NEEDS TO BE COORDINATED TO AVOID
 UNNECESSARY DELAYS AND CONFLICTS.)
  
 B) MECHANICAL PLAN CALLS FOR TWO "EXISTING A.H.U.".
 THIS IS MISLABELED. AIR HANDLER UNITS ARE LOCATED
 INSIDE THE HOUSE. COMPRESSORS ARE THE ONES THAT ARE
 LOCATED OUTSIDE. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- MECHANICAL PLAN DOESN'T SHOW LOCATION OF THE EXHAUST
 FAN FOR THE NEW BATHROOM AND FOR THE EXISTING BATHROOM
 WHICH WINDOW WAS CLOSED. REVISE AS REQUIRED. A/C PLANS
 AND ENGINEER'S PLANS NEED TO MATCH. . SEC. 107.2.1 CITY
 AMENDMENTS.
  
 4- INFORMATION SHOWN ON THE MECHANICAL PLAN M.1 AND
 INFORMATION SHOWN ON THE ELECTRICAL PLAN ON SHEET E-1
 DOESN'T MATCH. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  