| 2015-08-25 08:58:18 | RESIDENTIAL (R3) ADDITION SECOND MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- PERSON RESPONSIBLE FOR THE M.1 DRAWING TO PROVIDE |
| | NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 2- A) EQUIPMENT INFORMATION IS NOT CLEAR. DRAWINGS S-1 |
| | AND E-1 SHOW ONE A/C UNIT. DRAWING M.1 SUBMITTED SHOWS |
| | TWO A/C UNITS. COORDINATE ALL PLANS AS REQUIRED TO |
| | MATCH. SEC. 107.2.1 CITY AMENDMENTS. (REPEAT COMMENT. |
| | MECHANICAL PLAN AND ENGINEER'S PLANS DON'T MATCH. |
| | INFORMATION NEEDS TO BE COORDINATED TO AVOID |
| | UNNECESSARY DELAYS AND CONFLICTS.) |
| | |
| | B) MECHANICAL PLAN CALLS FOR TWO "EXISTING A.H.U.". |
| | THIS IS MISLABELED. AIR HANDLER UNITS ARE LOCATED |
| | INSIDE THE HOUSE. COMPRESSORS ARE THE ONES THAT ARE |
| | LOCATED OUTSIDE. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 3- MECHANICAL PLAN DOESN'T SHOW LOCATION OF THE EXHAUST |
| | FAN FOR THE NEW BATHROOM AND FOR THE EXISTING BATHROOM |
| | WHICH WINDOW WAS CLOSED. REVISE AS REQUIRED. A/C PLANS |
| | AND ENGINEER'S PLANS NEED TO MATCH. . SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 4- INFORMATION SHOWN ON THE MECHANICAL PLAN M.1 AND |
| | INFORMATION SHOWN ON THE ELECTRICAL PLAN ON SHEET E-1 |
| | DOESN'T MATCH. REVISE AS REQUIRED TO MATCH. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |