Plan Review Notes
Plan Review Notes For Permit 14110845
Permit Number 14110845
Review Stop M
Sequence Number 1
Notes
Date Text
2014-12-22 12:18:50RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PERSON RESPONSIBLE FOR THE M.1 DRAWING TO PROVIDE
 NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- EQUIPMENT INFORMATION IS NOT CLEAR. DRAWINGS S-1 AND
 E-1 SPECIFY TWO A/C UNITS. ONE AS EXISTING AND THE
 OTHER ONE AS PROPOSED. DRAWING M.1 SUBMITTED SPECIFIES
 "EXISTING A.H.U." FOR BOTH UNITS. COORDINATE ALL PLANS
 AS REQUIRED TO MATCH. CLEARLY, IDENTIFY WHAT'S NEW AND
 WHAT'S EXISTING. SEC. 107.2.1 CITY AMENDMENTS.
  