2014-12-19 10:48:47RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1 BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.
  
 2- SHEET S-1:
 A) CONSTRUCTION OF NEW WALL ADJACENT TO THE EXISTING
 WALL IS NOT CLEAR. PROVIDE CLEAR WALL SECTION FROM
 FOOTING TO ROOF PARAPET AND PROVIDE CLEAR
 SPECIFICATIONS. HOW IS THE NEW WALL ATTACHED TO
 EXISTING WALL. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 B) REVISE THE TYPE OF ALTERATION SPECIFIED UNDER THE
 SCOPE OF WORK BUILDING CODES INFORMATION. THIS IS NOT
 ALTERATION LEVEL 3. THIS IS AN ADDITION. SEC. 407 OF
 2010 FBC-EXISTING BUILDING.
  
 C) REVISE/CLARIFY THE DESIGN LOADS INFORMATION SHOWN ON
 THE RIGHT BOTTOM OF DRAWING S-1. SPECIFY ROOF LOADS FOR
 TYPE OF PROPOSED ROOF (FLAT) AND FOR FLOOR JOISTS (NOT
 FLOOR TRUSSES). SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 D) SPECIFY ROOF SLOPE. SEC. R905.11.1 OF 2010
 FBC-RESIDENTIAL.
  
 3- EXISTING WINDOW IN MASTER BEDROOM IS PROPOSED TO BE
 REMOVED TO ALLOW FOR THE NEW MASTER BATHROOM ADDITION.
 CLEARLY IDENTIFY ON PLANS HOW IS THE ALTERED MASTER
 BEDROOM COMPLYING WITH THE EGRESS REQUIREMENTS OF SEC.
 R310 OF 2010 FBC-RESIDENTIAL.
  
 4- IDENTIFY ON PLANS THE ROOM LOCATED ON THE RIGHT HAND
 SIDE OF EXISTING BATHROOM. IS THIS A BEDROOM?.
 ACCORDING TO PLANS THE WINDOWS IN THIS ROOM ARE GOING
 TO BE REPLACED. SPECIFY TYPE AND SIZE OF EXISTING
 WINDOW AND PROPOSED TYPE AND SIZE TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010
 FBC-RESIDENTIAL.
  
 5- THERE WAS A WINDOW ON THE EXISTING BATHROOM THAT IS
 PROPOSED TO BE BLOCKED TO ALLOW FOR THE NEW MASTER
 BATHROOM ADDITION. CLEARLY SPECIFY ON PLANS HOW IS THIS
 BATHROOM COMPLYING WITH THE MECHANICAL VENTILATION
 REQUIRED BY SEC. R303.3 OF 2010 FBC-RESIDENTIAL.
  
 6- SPECIFY CARBON MONOXIDE ALARMS IN ALL SLEEPING ROOMS
 AS REQUIRED BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ROOF
 DRAINAGE SHOWING COMPLIANCE WITH THE ROOF DRAINAGE SEC.
 R903.4 OF 2010 FBC-RESIDENTIAL. SPECIFY SIZE OF ROOF
 DRAIN OR SCUPPER. SPECIFY SIZE OF DOWNSPOUT.
 INFORMATION SHOWN ON THE SOUTH ELEVATION IS NOT CLEAR.
 WHAT'S A "BRAKE METAL LEADER BOX & DOWNSPOUT." ??? WHY
 IS IT SHOWN ABOVE THE FINISH ROOF LINE? ???
  
 8- ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT AWAY
 FROM THE STRUCTURE. REVISE PLANS AS REQUIRED.
  
 9- NEED TO SPECIFY OVERFLOW SCUPPERS SIZE AND LOCATION
 AS REQUIRED BY SEC. R903.4.1 OF 2010 FBC-RESIDENTIAL.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE GUARDRAILS SHOWN ON THE NEW WOOD
 DECK SHOWING COMPLIANCE WITH THE LIVE LOADS OF TABLE
 R301.5 AND SEC. R312 OF 2010 FBC-RESIDENTIAL.
  
 11- REVISE/CLARIFY INFORMATION ON INTERIOR PARTITION
 DETAIL ON SHEET S-1:
 A) THERE IS NOT EXISTING CONCRETE SLAB. THIS IS AN
 ADDITION. SEE FLOOR FRAMING PLAN AND REVISE THE
 FLOORING AND BASE PLATE FASTENING SPECIFICATIONS. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 B) CLARIFY NOTE STATING "8D RING SHANK NAILS AT EA.
 TRUSS OR 24" O.C. MAX". CLEARLY SPECIFY TOP PLATE
 FASTENING TO THE 2X12 ROOF RAFTER. SPECIFICATIONS TO
 MATCH INFORMATION SHOWN ON THE ROOF FRAMING PLAN. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 12- PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE NEW ROOF CROSS VENTILATION AS
 REQUIRED BY SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 13- NEW WOOD DECK SHOWN ON FOUNDATION PLAN ON SHEET
 S-2:
 A)PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 THAT MATCH THE PROPOSED WOOD DECK. INFORMATION
 SUBMITTED IS GENERIC DOESN'T MATCH PROPOSED DECK AND IS
 MISSING ALL THE STRUCTURAL INFORMATION. CLEARLY SPECIFY
 ALL MEMBERS SIZES (POSTS, BEAMS, ETC)AND SPACING,
 NUMBER OF FRAMING MEMBERS AT THE PERIMETER, ALL
 FASTENERS, ETC. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE MANUFACTURER'S COMPLETE SPECIFICATIONS (2
 COPIES) FOR THE 12" X 12" PRE-FAB CONC. PADS SPECIFIED
 ON FOUNDATION PLAN TO VERIFY COMPLIANCE WITH SEC. R301.
  
 14- FOUNDATION PLAN ON SHEET S-2: CLARIFY WHY IS THERE
 AN OPENING SHOWN ON THE SOUTH SIDE WALL OF THE STEM
 WALL. WHAT IS THIS OPENING FOR?. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 15- FLOOR FRAMING PLAN ON SHEET S-2: :
 A) CLEARLY SPECIFY SIZES AND LOCATION OF ALL
 UNDER-FLOOR SPACE VENTILATION OPENINGS SHOWING
 COMPLIANCE WITH SEC R408 OF 2010 FBC-RESIDENTIAL. AND
 CLEARLY SPECIFY THE SIZE OF CRAWL SPACE ACCESS OPENING.
  
 B) PROVIDE SPECIFICATIONS FOR THE TYPE OF FLOOR JOIST
 TO BE USED TO SHOW COMPLIANCE WITH PROTECTION OF WOOD
 AS REQUIRED BY SEC. R317 OF 2010 FBC-RESIDENTIAL.
  
 16- WALL SECTION ON SHEET S-2:
 A) SPECIFY STUCCO THICKNESS. TABLE R702.1(1) OF 2010
 FBC-RESIDENTIAL.
  
 B) SPECIFY 2 LAYERS OF WATER RESISTANT BARRIER AS
 REQUIRED BY SEC. R703.6.3 OF 2010 FBC-RESIDENTIAL.
  
 C) SPECIFY HOW ARE THE TWO BOTTOM PLATES ATTACHED TO
 THE STEM WALL TO SHOW COMPLIANCE WITH SEC. R601.2 OF
 2010 FBC-RESIDENTIAL.
  
 D) SPECIFY THE HORIZONTAL REINFORCEMENT FOR STEM WALL
 "U" BLOCK. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 E) PROVIDE COMPLETE SPECIFICATIONS FOR THE FASTENING OF
 THE PARAPET WALL. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 17- WINDOW FRAMING DETAIL AND DOOR FRAMING DETAIL ON
 SHEET S-2: REVISE INFORMATION TO MATCH PROPOSED
 CONSTRUCTION. REVISE THE FLOOR TYPE, STUDS SIZES, ROOF
 FRAMING, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 18- ROOF FRAMING DETAIL ON SHEET S-2: SPECIFY THE ROOF
 SHEATHING NAIL TYPE AND SIZE AND SPACING AS REQUIRED BY
 SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL.
  
 19- INFORMATION ON PLANS NEED TO MATCH INFORMATION ON
 THE ENERGY CALCULATIONS SUBMITTED. SPECIFY INSULATION
 OVER CRAWL SPACE. REVISE R VALUE FOR EXTERIOR WALLS.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 20- PROVIDE MANUFACTURER SPECS FOR THE WINDOWS AND
 DOORS U-FACTOR AND SHGC FACTOR SHOWING COMPLIANCE WITH
 THE VALUES SPECIFIED ON THE ENERGY CALCULATIONS
 SUBMITTED. SEC. R103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 21- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE ENERGY CALCULATIONS FOR THE ADDITION ONLY OR
 FOR ENTIRE HOUSE. DON'T MIX MATCH BOTH. COOLING AND
 HEATING INFORMATION SHOWN ON ITEMS #12 AND #13 DON'T
 CORRESPOND TO THE ADDITION ALONE. REVISE AS REQUIRED.
 SEC. 101.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE FLOOR TYPE INFORMATION ON ITEM #8. THERE IS
 NO CONCRETE SLAB ON GRADE. SEE PLANS. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 C) REVISE UNDER ATTIC INFORMATION ON ITEM # 10.
 COORDINATE WITH PLANS IF ATTIC VENTILATION IS PROVIDED
 OR NOT. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 D) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH
 ACTUAL SEPARATION SHOWN ON PLANS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 E) WALLS INFORMATION ON PAGE 3 OF 5 IS MISSING THE
 SOUTH WALL INFORMATION. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 F) WINDOWS AREA ON PAGE 3 OF 5 DOESN'T MATCH ACTUAL
 WINDOW AREA. SEE PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 ****NOTE: THIS IS A CONTRIBUTING HISTORIC HOUSE. IT'S
 EXEMPT FROM THE ENERGY CODE. ENERGY CALCULATIONS ARE
 NOT REQUIRED. IF YOU ARE GOING TO SUBMIT THEM, THEN
 MAKE ABOVE CORRECTIONS.
  
 22- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF: NOA 13-0424.14 SUBMITTED EXPIRED ON
 11/06/14. NEED TO PROVIDE CURRENT NOA.
 IN ADDITION: (1) CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED. AND, PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
  
 B) BIFOLD EXTERIOR DOOR AS SHOWN ON PLANS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND ALL DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ENGINEER MAY LIST THE FLORIDA PRODUCT
 APPROVAL NEXT TO THE SPECIFIED CONNECTOR.
  
 23- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 OF CITY
 AMENDMENTS.
  
 24- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPDATED TO $24,000. THE VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS. THE PERMIT FEE BALANCE IS
 $556.80.
  
 ***PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
  