| Plan Review Notes For Permit 14110844 |
| Permit Number |
14110844 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-26 06:52:43 | 1) SUBMIT MANUF. SPEC. SHEETS/INSTALLATION MANUAL FOR | | | THE GENERATOR. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 2) SHT. E-2 NOTE #6 STATES THAT THE LP GAS LINE IS TO | | | BE EXTENDED. INDICATE THE LINEAL FOOTAGE THAT THE GAS | | | LINE WILL BE EXTENDED AND THE TYPE OF PIPE TO BE USED. | | | SUBMIT A GAS RISER DIAGRAM SHOWING THE BTU LOAD OF THE | | | GENERATOR, THE TOTAL DISTANCE FROM THE LP TANK TO THE | | | GENERATOR, PSI OF THE GAS AND LOCATION OF ALL | | | REGULATORS. NFPA 58. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|