2014-11-26 06:52:431) SUBMIT MANUF. SPEC. SHEETS/INSTALLATION MANUAL FOR
 THE GENERATOR. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT. E-2 NOTE #6 STATES THAT THE LP GAS LINE IS TO
 BE EXTENDED. INDICATE THE LINEAL FOOTAGE THAT THE GAS
 LINE WILL BE EXTENDED AND THE TYPE OF PIPE TO BE USED.
 SUBMIT A GAS RISER DIAGRAM SHOWING THE BTU LOAD OF THE
 GENERATOR, THE TOTAL DISTANCE FROM THE LP TANK TO THE
 GENERATOR, PSI OF THE GAS AND LOCATION OF ALL
 REGULATORS. NFPA 58.
  