Plan Review Notes
Plan Review Notes For Permit 14110844
Permit Number 14110844
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-05 16:32:4912/5/2014
 PROJECT: GENERATOR REPLACEMENT
 PERMIT#: 14110844
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE RISER DIGRAM TO INDICATE ATS UTILITY (NORMAL
 SIDE) FEED. BACK UP GENERATOR FEEDER IS CURRENTLY DRAWN
 TO CONNECT DIRECTLY TO ANOTHER 350AMP MCB AND THERE IS
 NO INDICATION OF WHAT IS FEEDING THE UTILITY SIDE OF
 THE ATS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  