| Plan Review Notes For Permit 14110818 |
| Permit Number |
14110818 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-02-19 12:40:32 | 1) THE MATCH LINES ADDED ON SHEETS P201 THRU P206 HAVE | | | NOT ACCOMPLISHED THE INTENT FOR CLARIFICATION.THE ADDED | | | NOTE"SEE FLOOR PLAN 101 FOR CONTINUATION" REFERENCES | | | THE CORRECT SHEET BUT SHEET 101 DOES NOT SHOW THE | | | CONTINUATION OF THE PIPING FOR THE DIFFERENT AREAS. | | | ALTHOUGH I APPLAUD THE EFFORT TO CLARIFY DETAILS, THE | | | CHANGES HAVE CAUSED ADDITIONAL CONFUSION. SHT. P101 | | | SHOWS VERY LITTLE PIPNG, AND ROOMS/AREAS ARE NOT | | | NUMBERED, SO IT IS VERY DIFFICULT TO LOCATE THE | | | CONTINUATION OF PIPNG FROM ONE SHEET OR AREA TO THE | | | NEXT. THE MATCH LINES ARE NOT IDENTIFIED WITH A LETTER | | | OR NUMBER SO IT IS VERY DIFFICULT TO FOLLOW THE PIPING | | | SYSTEMS. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 2) SHT.P3.04 - IN MY PREVIOUS PLAN REVIEW, COMMENT # | | | 11, I REQUESTED TO SHOW THE CONTINUATION / CONNECTION | | | POINTS OF THE 2" & 3" VENTS ON THE GREASY WASTE | | | SYSTEM.THE NOTE "SEE PLANS FOR CONTINUATION" DOES NOT | | | PROVIDE MUCH HELP.IF THE SPECIFIC PLAN COULD BE | | | IDENTIFIED FOR WHERE THESE VENTS CONNECT I COULD LOCATE | | | & REVIEW THESE ITEMS MUCH QUICKER. | | | 3) SHT. P3.04 - THERE IS A SECTION OF VENT THAT GOES | | | NOWHERE. IT APPEARS TO BE A TYPO ERROR. | | | | | | PLEASE CONTACT ME SO WE CAN SET UP A MEETING TO DISCUSS | | | THESE COMMENTS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|