Plan Review Notes
Plan Review Notes For Permit 14110798
Permit Number 14110798
Review Stop P
Sequence Number 2
Notes
Date Text
2015-01-13 13:19:531) THE PLANS ONLY SHOW A MEN'S RESTROOM BEING
 RENOVATED. IS THERE A FEMALE RESTROOM BEING RENOVATED?
 IF SO, SUBMIT PLANS FOR THAT RESTROOM RENOVATION. 2ND
 REQUEST.
 2) INDICATE ON THE PLANS THE SPECIFIC SCOPE OF WORK TO
 BE DONE TO THIS RESTROOM. IS IT NEW OR EXISTING? ARE
 JUST THE PLUMBING FIXTURES BEING REPLACED? THE PLANS
 ARE VAGUE AS TO THE SCOPE OF WORK BEING DONE. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.2ND REQUEST.
 3) MOUNTING HEIGHTS SHALL COMPLY WITH THE 2010 FL.
 ACCESSIBILITY CODE. CHAPTER 3 AND CHAPTER 6. THE GRAB
 BARS SHALL BE MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT THE CENTERLINE AS SHOWN. THE TOILET PAPER
 DISPENSER SHALL BE A MAXIMUM OF 48 INCHES ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE DISPENSER PER
 FAC SEC.604.7.
 5) SHOW THE REQUIRED CLEAR FLOOR SPACES FOR THE
 LAVATORY AND THE WATER CLOSET ON THE PLANS. COMPLY WITH
 FAC SECS.306 & 604.2ND REQUEST.
 6) THE DRINKING FOUNTAIN/WATER COOLER CANNOT BE LOCATED
 IN THE RESTROOM PER THE 2010 FPC SEC. 410.2.2ND
 REQUEST.
 7) SHT. M-1 - SIZE ALL SECTIONS OF THE VENT SYSTEM.
 COMPLY WITH FPC TABLE 916.1. 2ND REQUEST.
 8) SIZE THE WET SECTION OF ALL WASTE /SOIL STACKS.TABLE
 710.1. 2ND REQUEST.
 9) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS PER
 FPC SEC. 708.3.4.2ND REQUEST.
 10) SUBMIT A WATER RISER DIAGRAM FOR ANY CHANGES BEING
 MADE TO THE PIPING SYSTEM. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3. 2ND REQUEST
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  